Model No.: JTD 12kv 1250A 20KA vacuum interrupter for Solid embedded poles
Rated voltage: 12 KV
Rated current: 1250A
Rated power frequency withstand voltage (1 min): 42 KV
Rated lightning impulse withstand voltage: 75 KV
Rated short circuit breaking current: 20KA
Rated short circuit making current(peak value): 50KA
Breaking operations under rated short circuit breaking current: 30 times
Rated short time withstand current: 20KA
Rated withstand current(peak value): 50KA
Rated duration of short circuit: 4 s
Mechanical life: 20,000 times
Closing force due to bellows and atmosphere: 70±40 N
Force required to hold contacts opening at full stroke: 120±50 N
Circuit resistance at lowest rated contacts force: =35µO
Storage life: 20 years
Limiting abrasion of contacts: 3 mm
Weight of moveable parts: =0.7kg
Mechanical requiements of vacuum circuit breaker
Clearance between opening contacts: 7±1 mm
Average opening speed: 1.0±0.25 m/s
Average closing speed: 0.65±0.15 m/s
Rated contacts pressure: 1600±100 N
Contacts bouncing duration at closing operation: =2 ms
Contacts re-bouncing clearance at opening operation: =2 mm
Synchronism of three phases: =1 ms
Supplier: Branded consumer electronics, televisions, cameras, home appliances, car audio systems, hair curlers, hair trimmers, hair clippers, hair straighteners, beard trimmers, shavers, vacuum cleaners, air purifiers, blenders, mixers, juicers etc, mg3710/15 mg3730/15 mg5720/15 mg7720/15 bt1233/14 bt3206/14 bt3216/14
Supplier: Woven/knit and non woven fabric and its relative products like disposable medical products, home/hotel textiles, essential oils, household appliances, kitchenware, fiberglass mesh cloth, etc.
Supplier: Juicer, mixer grinder, pressure cooker, electric iron, toaster, frying pan, water purifier, water dispenser, mixer/blender, dry iron, kettle, gas stove , non stick cookware, water heater, air cooler, water purifier, electric chimney system ceiling fan others, kitchen appliances, range hood
Model No.: TD 12kv 1250A 31.5KA (JUC618) vacuum interrupter for VCB Main technical parameters Rated voltage: 12 KV Rated current: 1250A Rated power frequency withstand voltage: 42 KV Rated lightning impulse withstand voltage: 75 KV Rated short circuit breaking current: 31.5KA Rated short circuit making current(peak value): 80KA Breaking operations under rated short circuit breaking current: 30 times Rated short time withstand current: 31.5KA Rated withstand current(peak value): 80KA Rated duration of short circuit: 4S Mechanical life: 20,000 times Closing force due to bellows and atmosphere: 120±50N Force required to hold contacts opening at full stroke: 190±50N Circuit resistance at lowest rated contacts force: =20µO Storage life: 20 years Limiting abrasion of contacts: 3 mm Mechanical requiements of vacuum circuit breaker Clearance between opening contacts: 11±1 mm Average opening speed(Contacts closing position~75% contacts opening distance): 1.1±0.2 m/s Average closing speed(30% contacts opening distance~contacts closing position): 0.6±0.2 m/s Rated contacts pressure: 3150±200 N Contacts bouncing duration at closing operation: =2 ms Contacts re-bouncing clearance at opening operation: =2 mm Synchronism of three phases: =1 ms
Model No.: TD 12kv 1250A 31.5KA (JUC619A) vacuum interrupter for VCB Main technical parameters Rated voltage: 12 KV Rated current: 1250A Rated power frequency withstand voltage: 48 KV Rated lightning impulse withstand voltage: 85 KV Rated short circuit breaking current: 31.5KA Rated short circuit making current(peak value): 80KA Breaking operations under rated short circuit breaking current: 30 times Rated short time withstand current: 31.5KA Rated withstand current(peak value): 80KA Rated duration of short circuit: 4 s Mechanical life: 10,000 times Closing force due to bellows and atmosphere: 120±50 N Force required to hold contacts opening at full stroke: 190±50 N Circuit resistance at lowest rated contacts force: =20µO Storage life: 20 years Limiting abrasion of contacts: 3 mm Mechanical requiements of vacuum circuit breaker Clearance between opening contacts: 11±1 mm Average opening speed(Contacts closing position~75% contacts opening distance): 1.1±0.2 m/s Average closing speed(30% contacts opening distance~contacts closing position): 0.6±0.2 m/s Rated contacts pressure: 3150±200 N Contacts bouncing duration at closing operation: =2 ms Contacts re-bouncing clearance at opening operation: =2 mm Synchronism of three phases: =1 ms * It Needs additional insultating protection.
Model No.: TD 12kv 1250A 25KA (JUC613) vacuum interrupter for VCB Main technical parameters Rated voltage: 12 KV Rated current: 1250A Rated power frequency withstand voltage: 42 KV Rated lightning impulse withstand voltage: 75 KV Rated short circuit breaking current: 25KA Rated short circuit making current(peak value): 63KA Breaking operations under rated short circuit breaking current: 30 times Rated short time withstand current: 25KA Rated withstand current(peak value): 63KA Rated duration of short circuit: 4S Mechanical life: 20,000 times Closing force due to bellows and atmosphere: 120±50N Force required to hold contacts opening at full stroke: 190±50N Circuit resistance at lowest rated contacts force: =20µO Storage life: 20 years Limiting abrasion of contacts: 3 mm Mechanical requiements of vacuum circuit breaker Clearance between opening contacts: 11±1mm Average opening speed(Contacts closing position~75% contacts opening distance): 1.1±0.2 m/s Average closing speed(30% contacts opening distance~contacts closing position): 0.6±0.2 m/s Rated contacts pressure: 2000±200N Contacts bouncing duration at closing operation: =2ms Contacts re-bouncing clearance at opening operation: =2mm Synchronism of three phases: =1ms
Photocells Fans & ventilation, Hazardous area lighting Industrial plugs & sockets Industrial & commercial Lamps Light fittings: fluorescent, weatherproof & floodlighting Refrigeration & air conditioning spares Water heating elements Wiring accessories MCB's Circuit breaker Vacuum Breakers Control transformers Fuses & load break devices Hazardous area products Industrial beacons Industrial sounders, buzzers Industrial surge protection Safety switches Clamp meters Multi-meters Testers Semiconductors: thyristors, rectifiers Pressure switches Solenoid & pilot valves Photoelectric Sensors
HCJ3 12KV 630A vacuum interrupter for vacuum contactor 1. Brief introduction The interrupter adoption porcelain and ceramics makes to insulate the outer shell. Contact is WCCu metal alloy material advanced technique of adoption Including bulk small. Breaking the abiliting strong the life span is long, maintenanle is simple ,no explosion dangerous, no contaminate and the noise is low . The pack vacuum contactor can operate the ebery kind of electric appliances equipments, and fuse match f-c cabinet 2. Vacuum Tube main technique parameter Rated voltage: 12 kv Rated cureent: 630A Rated making current: 6.3KA Rated breaking current: 5.04KA Limiting breaking current: 6.3KA Rated short-time withstand current: 6.3KA Rated short-time withstand voltage: 42 kv Rated lighting impulse voltage: 75 kv Circuit resistance at lowest rated contacts force: =80µO Electrical life: 250,000 times Mechanical life: 5000,000 times Closing force due to bellows and atmosphere: 70±20 N Force required to hold contacts open at full stroke: 100±30 N Limiting abrasion of contacts: 3 mm Internal gas pressure: =1.33×10-3 Pa Storage life: 20 years
Model No.: TD 12kv 1600A 31.5KA (JUC618A) vacuum interrupter for VCB Main technical parameters Rated voltage: 12 KV Rated current: 1600A Rated power frequency withstand voltage: 42 KV Rated lightning impulse withstand voltage: 75 KV Rated short circuit breaking current: 31.5KA Rated short circuit making current(peak value): 80KA Breaking operations under rated short circuit breaking current: 30 times Rated short time withstand current: 31.5KA Rated withstand current(peak value): 80KA Rated duration of short circuit: 4 s Mechanical life: 20,000 times Closing force due to bellows and atmosphere: 120±50 N Force required to hold contacts opening at full stroke: 190±50 N Circuit resistance at lowest rated contacts force: =20µO Storage life: 20 years Limiting abrasion of contacts: 3 mm Mechanical requiements of vacuum circuit breaker Clearance between opening contacts: 11±1 mm Average opening speed(Contacts closing position~75% contacts opening distance): 1.1±0.2 m/s Average closing speed(30% contacts opening distance~contacts closing position): 0.6±0.2 m/s Rated contacts pressure: 3150±200 N Contacts bouncing duration at closing operation: =2 ms Contacts re-bouncing clearance at opening operation: =2 mm Synchronism of three phases: =1 ms