Model
Item AL-15W
Nominal cooling capacity kcal/h 35948
Kw 41.8
Input power kw 16.42
Power supply 3pH~380V 50Hz
Refrigerant type R22
Type of control thermostatic expansion valve
Compressor type hermetic scroll(piston)
Power(kw) 13.72
Condenser type finned copper tube + low noise outer rotor fan
Cooling air flow(m3/h) 15000
Evaporator type tank with coil
Chilled fluid flow(m3/h) 7.2
Volume(L) 270
Inlet and outlet pipe diameter (inch) 2
Drain(inch) 1
Pump power (kw) 1.5
Lift(m) 26
Flow switch On >16L/min, Off <10L/min
Safety protection compressor over temperature, over current, high and low pressure, over temperature, flow Switch, phase sequence, phase-missing, exhaust overheating.
Weight kg 750
Dimension mm 1800*990*1680.
Note: 1. Nominal cooling capacity is according to:
Inlet chilled fluid temperature: 12degree
Outlet chilled fluid temperature: 7degree
Inlet cooling air temperature: 30degree
Outlet cooling air temperature: 35degree
2. Working range:
The temperature range of chilled fluid is from 5degree to 35degree;
Temperature difference between inlet and outlet chilled fluid is from 3degree to 8degree.
The machine should be used while the ambient temperature at or below 35degree.
Supplier: Chiller, industrial chiller, water chiller, laser chiller, air cooled chiller