HCJ5 1.14kv 1000A vacuum interrupter for vacuum contactor
1. Brief introduction
The interrupter adoption porcelain and ceramics makes to insulate the outer shell. Contact is WCCu metal alloy material advanced technique of adoption Including bulk small. Breaking the abiliting strong the life span is long, maintenanle is simple, no explosion dangerous, no contaminate and the noise is low. It is extensive to used for coal mine , chemical engineering, Petroleum metallurgy etc. department, more than keeping with at the multifarious operation with the bad place usage of environmen
2. Vacuum Tube main technical parameter
Rated voltage: 1.14 kv
Rated current: 1000 A
Rated put through current: 10000A
Rated breaking current: 8000A
Limiting breaking current: 10000A
Rated short-time withstand current: 8000A
Rated short-time withstand voltage(1 min): 10 kv
Mechanical life: 1000000 times
Rated breaking time AC3: 150000 times
Rated breaking time AC4: 6000 times
Automatic closing force of the contacts: 70±20 N
Force required to hold contacts open at full stork: 90±20 N
Contact automatic blocking ability loop electrical resistance: 80
Contact-wear allowance thickness: 2 mm
Shelf life: 20 years
Internal gas pressure: 1.3310-3 Pa
HCJ5 1.14kv 125A vacuum interrupter for vacuum contactor
1. Brief introduction
The interrupter adoption porcelain and ceramics makes to insulate the outer shell. Contact is WCCu metal alloy material advanced technique of adoption Including bulk small. Breaking the abiliting strong the life span is long, maintenanle is simple, no explosion dangerous, no contaminate and the noise is low. It is extensive to used for coal mine , chemical engineering, Petroleum metallurgy etc. department, more than keeping with at the multifarious operation with the bad place usage of environment
2. Vacuum Tube main technique parameter
Rated voltage: 1.14 kv
Rated current: 125A
Rated making current: 1250A
Rated breaking current: 1000A
Limiting breaking current: 1250A
Rated short-time withstand current: 1000A
Rated short-time withstand voltage: 10 kv
Mechanical life: 1000000 times
Breaking operations AC3: 150000 times
Breaking operations AC4: 6000 times
Automatic closing force of the contacts: 25±10 N
Force required to hold contacts open at full stork: 40±10 N
Circuit resistance at lowest rated contacts force: 120
Limiting abrasion of contacts: 2 mm
Storage life: 20 years
Internal gas pressure: 1.33 10-3 Pa
HCJ3 7.2kv 630A vacuum interrupter for vacuum contactors
1. Brief introduction
The interrupter adoption porcelain and ceramics makes to insulate the outer shell. Contact is WCCu metal alloy material advanced technique of adoption Including bulk small. Breaking the abiliting strong the life span is long maintenance is simple .no explosion dangerous no contaminate and the noise is low . The pack vacuum contactor can operate the ebery kind of electric appliances equipments, and fuse match f-c cabinet
2. Vacuum Tube main technique parameter
Rated voltage: 7.2 kv
Rated current: 630A
Rated making current: 6.3KA
Rated breaking current: 5.04KA
Limiting breaking current: 6.3KA
Rated short-time withstand current: 6.3KA
Rated short-time withstand voltage: 32 kv
Rated lighting impulse voltage: 60 kv
Circuit resistance at lowest rated contacts force: 80
Electrical life: 250,000 times
Mechanical life: 500,000 times
Closing force due to bellows and atmosphere: 70±20 N
Force required to hold contacts open at full stroke: 100±30 N
Limiting abrasion of contacts: 3 mm
Internal gas pressure: 1.3310-3 Pa
Storage life: 20 years
HCJ3 12KV 630A vacuum interrupter for vacuum contactor
1. Brief introduction
The interrupter adoption porcelain and ceramics makes to insulate the outer shell. Contact is WCCu metal alloy material advanced technique of adoption Including bulk small. Breaking the abiliting strong the life span is long, maintenanle is simple ,no explosion dangerous, no contaminate and the noise is low . The pack vacuum contactor can operate the ebery kind of electric appliances equipments, and fuse match f-c cabinet
2. Vacuum Tube main technique parameter
Rated voltage: 12 kv
Rated cureent: 630A
Rated making current: 6.3KA
Rated breaking current: 5.04KA
Limiting breaking current: 6.3KA
Rated short-time withstand current: 6.3KA
Rated short-time withstand voltage: 42 kv
Rated lighting impulse voltage: 75 kv
Circuit resistance at lowest rated contacts force: 80
Electrical life: 250,000 times
Mechanical life: 5000,000 times
Closing force due to bellows and atmosphere: 70±20 N
Force required to hold contacts open at full stroke: 100±30 N
Limiting abrasion of contacts: 3 mm
Internal gas pressure: 1.3310-3 Pa
Storage life: 20 years
1.Introduction
JCZ5 7.2 kv vacuum contactor
HVJ6-7.2 series indoor high-voltage AC vacuum contactor has two types: One is Mechanical holding type, the other is Electromagnetic holding type. It is applicable for three-phase AC 50HZ power system of rated voltage 7.2KV and below and rated current up to 630 A to open and close circuit remotely and control electrical equipment like high-voltage motor, transformer and capacitive load. It is especially suitable for fields operated frequently. The contactor uses the international fashionable up and down structure arrangement and has the advantages of small, light, easy to maintain and form a complete set of F-C circuit equipment.
2. Service condition
a) Ambient air temperature: -25- +40.
b) Altitude not exceed 2000m
c)Humidity:
-Relative humidity: daily mean not higher than 95,monthly mean not higher than 90;
-Aqueous vapor pressure: daily mean not exceed 2.2 KP, monthly mean not exceed 1.8 KP
Ambient air should not be obviously polluted by corrosive or flammable gas or vapor;
C)Free of frequent severe vibration; When running, angle of inclination between installation surface and horizontal plane should not exceed 5.
Main technical parameters
Rated voltage: 7.2 kv
Control voltage: 110V, 220V
Rated current: 200A, 400A, 630A
Contacts separation: 4.5+1-0.5mm
Over travel: 1.5±0.5 mm
Main circuit power frequency voltage withstand: 32000 V
Auxiliary circuit power frequency withstand voltage: 2500 V
Control circuit power frequency withstand voltage: 2000 V
Making capacity: 10le,100 times
Breaking capacity: 8le, 25 times
Limit breaking current(A): 10le
Mechanical life times: 30104
Weight: 28KG
1.Introduction
JCZ5 12kv vacuum contactor
HVJ6-12 series indoor high-voltage AC vacuum contactor has two types: One is Mechanical holding type, the other is Electromagnetic holding type. It is applicable for three-phase AC 50HZ power system of rated voltage 12KV and below and rated current up to 630 A to open and close circuit remotely and control electrical equipment like high-voltage motor, transformer and capacitive load. It is especially suitable for fields operated frequently. The contactor uses the international fashionable up and down structure arrangement and has the advantages of small, light, easy to maintain and form a complete set of circuit equipment.
2. Service condition
a) Ambient air temperature: -25- +40.
b) Altitude not exceed 2000m
c)Humidity:
-Relative humidity: daily mean not higher than 95,monthly mean not higher than 90;
-Aqueous vapor pressure: daily mean not exceed 2.2 KP, monthly mean not exceed 1.8 KP
Ambient air should not be obviously polluted by corrosive or flammable gas or vapor;
C)Free of frequent severe vibration; When running, angle of inclination between installation surface and horizontal plane should not exceed 5.
Main technical parameters
Rated voltage: 12000 v
Control circuit: 110V 220V
Rated current: 200A 400A 630A
Contacts separation: 5+1-0.5 mm
Over travel: 1.5±0.5 mm
Main circuit power frequency withstand voltage: 42000 v
Auxiliary circuit power frequency voltage withstand: 2500 v
Control circuit power frequency voltage withstand: 2000 V
Making capacity: 10le,100 times
Breaking capacity: 8le, 25 times
Limit breaking current(A): 10le
Mechanical life times: 30104
Weight: 32KG
1. Introduction
HVD7 33KV 36kv outdoor HV AC vacuum circuit breaker VCB has many visual advantages like reasonable design, fashionable appearance, high safety and reliability, simple maintenance, long electric life. It is the ideal upgraded products of 35KV outdoor oil circuit breakers.
HVD7-40.5 vacuum circuit breaker is applicable for three-phase power system of AC 50HZ.It is used to make and break the load current ,overload current and short-circuit current.
2. Applicable environment
3.1The ambient temperature should be -30degree~ +40degree(-40degree in the frosty area);
3.2Altitude should not exceed 2000m(over 2000m is plateau type);
3.3The wind pressure should not exceed 700Pa(equal to wind speed 34m/s);
3.4Air pollution degree: 3,that of antifouling type:4;
3.5The installation site should be free from the fire, explosion, chemical corrosion and serious vibration.
1.Main technical parameters
Rated voltage: 33kv 36KV
1 minute power frequency withstand voltage, dry test: 95 kv
1 minute power frequency withstand voltage, wet test: 80 kv
Lightning impulse withstand voltage(peak value): 185 kv
Rated current: 1600A / 2000A
Rated short-circuit breaking current: 20KA, 25KA, 31.5KA
Rated short-circuit making current(peak): 50KA, 63KA, 80KA
Rated operating sequence: O-0.3s-CO-180s-CO
Rated short-time withstand current: 20KA, 25KA, 31.5KA
Rated peak withstand current: 50KA, 63KA, 80KA
Rated short-circuit duration: 4 s
Rated control voltage: AC220,110;DC220,110
Rated short-circuit breaking current break times: 20 times
Full-break time:
HVJ3 7.2KV VACUUM CONTACTOR
1. General
The vacuum contactor is mainly used in the power system with AC 50Hz and rated voltage 7.2kV, for making or breaking circuit and to make electromagnetic starter with suitable protective device and F-C switchgear.
2. Working condition:
1) Altitude should not be over 1,000m;
2) Ambient temperature: -5~40°C;
3) Average temperature in 24 hour not exceed 35°C;
4) When the highest temperature is 40°C, the relative humidity should not be higher than 50%;
5) Pollution degree: class 3
Main models and technical parameters
Rated voltage: 7.2 kv
Control voltage: 380/220/110
Rated current: 160A, 250A, 400A, 630A, 800A, 1000A
Clearance: 3.5±0.3 mm
Over travel: 2±0.2 mm
Pressure: >85N
Main circuit power frequency withstand voltage: 32000 v
Auxiliary circuit power frequency withstand voltage: 2500 v
Control circuit power frequency withstand voltage: 2000 v
Making capacity: 10Ie,100 times
Breaking capacity: 8Ie,25 times
Limit opening current(A): 10Ie
Overload: 8Ie,10 s
Mechanism life: 1 million times
Weight: 25.5 KG
Note: â??Ieâ?? represents the rated current of main circuit
HVJ3 12KV VACUUM CONTACTOR
Detailed product description:
The vacuum contactor is mainly used in the power system with AC 50Hz and rated voltage 12kV, for making or breaking circuit and to make electromagnetic starter with suitable protective device and F-C switchgear.
Working condition:
1) Altitude should not be over 1,000m;
2) Ambient temperature: -5~40°C;
3) Average temperature in 24 hour not exceed 35°C;
4) When the highest temperature is 40°C, the relative humidity should not be higher than 50%;
5) Pollution degree: class 3
.Main models and technical parameters
Rated voltage: 12 KV
Control voltage: 220/110/380
Rated current: 160A, 250A, 400A, 630A
Clearance: 5±0.5 mm
Over travel: 2±0.2 mm
Pressure: >85N
Main circuit power frequency withstand voltage: 42000 v
Auxiliary circuit power frequency withstand voltage: 2500 v
Control circuit power frequency withstand voltage: 2000 v
Making capacity: 10Ie,100 times
Breaking capacity: 8Ie,25 times
Limit opening current(A): 10Ie
Overload: 8Ie,10 s
Mechanism life: 1 million times
Weight: 30KG
Note: â??Ieâ?? represents the rated current of main circuit