HVD8 /LW8-40.5 type outdoor high-pressure sulfur hexafluoride circuit breaker is three-pole ac 50 hz, outdoor high voltage switch equipment, applicable to 40.5 kV power transmission and distribution system control and protection, can also be used to contact circuit breaker and movable capacitor group.
1ï¼?General
VS1 12KV vacuum circuit breaker VCB
HVD1-12(VS1-12) type indoor AC HV vacuum circuit breaker VCB (hereinafter referred to as circuit breaker) are suitable for 12kV air-insulated indoor switchgears, used as protection and control unit of power equipment of industrial& mining enterprise. Due to the super excellence, it is especially for location where requires the frequent operation of rated working current or multi breaking short circuit current.
The circuit breaker adopts the integrated design of operating mechanism and circuit breaker body, servers as not only fixed installation, but also the handcart unit through equipping with a special propelling mechanism.
2. Service conditions
3.1 Environment temperature:-15degree~+40degree;
3.2 Environment humidity: Daily average relative humidity:
Introduction
The LWâ?¡-252/4000-50 self-extinction Ac circuit breaker which is outdoor type finds its universal range of applications for the electrical system with elevation not greater than 2000m, ambient temperature not lower than-30C, dirtiness grade not higher than IV, alternating current 50Hz and the maximum voltage 126kV. It is used for cutting the rated current, malfunction current or switching the circuitry, to control and protect the electrical system, and it can also be used for connecting with the circuit breaker
The gas of the SF6 is employed as the arc-extinguishing medium and the dielectric material. The self-extinction technology and the new-type spring operating mechanism are introduced in the SF6 circuit breaker. Thus the circuit breaker has good qualities with long electrical life, low operation power, lower noise, high reliability, simple structure, small and long overhaul periods. It can fully replace the import same type one.
Caracteristic of structure
The breaker introduces the three-phase porcelain -pole with single interrupter structure. A spring operating mechanism is supplied and the mechanical action of the three-phase is inner connected. The gas of the SF6 is connected in the three-phase pole parts. A density controller with temperature compensation is used to monitor the gas of the SF6. Because of the self-extinction arc control principle and optimized design, it improves the efficiency of mechanism and reduces the operating power
Excellent breaking performance and long electrical life
High mechanism reliability and can be operated frequently
Because of the high insulation intensity and excellent contact movement, the breaking capacity current will not re-burn
The circuit breaker has high outer insulation level and ratio creepage distance is greater than. So it has excellent performance of resisting the filth and the earthquake, it is also can be operated safely under the environment with atrocious weather
High carrying ability: it has high capability margin as the temperature of each contact rises when it is under temperature rise test in the circuit (1.2 times 0f 4000A)
The appearance of the breaker is compact, and the installation and debugging is very easy. The maintenance is also very convenient
VED-12 series indoor high voltage vacuum circuit breaker is suitable for 12kV air-insulated indoor switchgear, used as protection and control unit of power equipment of industrial & mining enterprise. Due to the super excellence, it is especially suitable for locations where requires the frequent operation under rated working current or multiple breaking under short circuit breaking current. The circuit breaker adopts the integrated design of operating mechanism and circuit breaker body, servers as not only fixed installation, but also draw-out type equipped with a special propelling mechanism.
VED-12 has two main types. One is Draw-out type. Model No. is VED-12D. The other is Fixed type. Model No. is VED-12F.
Service conditions
1 Environment temperature:-15°C~+40°C;
2 Environment humidity: Daily average relative humidity:â?¤95%, monthly average relative humidity:â?¤90%; Daily average saturated vapor pressure:â?¤2.2Ã?10-3Mpa,monthly average saturated vapor pressure:â?¤1.8Ã?10-3Mpa;
3 Altitude: Not exceed 1000m;
4 Earthquake intensity: Not exceed°ree;
5 Service location: No water, flammable or explosive matter, chemical corrosive gas or drastic vibration.
Vacuum Circuit Breaker HVD7 40.5KV 1250A outdoor HV AC VCB from Hubei JUCRO Electric
1. Introduction
HVD7 40.5KV 1250A outdoor HV AC vacuum circuit breaker VCB has many visual advantages like reasonable design, fashionable appearance, high safety and reliability, simple maintenance, long electric life. It is the ideal upgraded products of 35KV outdoor oil circuit breakers.
HVD7-40.5 1250A vacuum circuit breaker is applicable for three-phase power system of AC 50HZ.It is used to make and break the load current ,overload current and short-circuit current.
2. Applicable environment
2.1The ambient temperature should be -30degree~ +40degree(-40degree in the frosty area);
2.2Altitude should not exceed 2000m(over 2000m is plateau type);
2.3The wind pressure should not exceed 700Pa(equal to wind speed 34m/s);
2.4Air pollution degree: 3,that of antifouling type:4;
2.5The installation site should be free from the fire, explosion, chemical corrosion and serious vibration.
Vacuum Circuit Breaker VCB HVD32 12KV 630A VCB from Hubei JUCRO Electric
1.General
HVD32 12KV This vacuum circuit breaker VCB is three-phase AC 50Hz, rated voltage 12 kV outdoor high voltage switch equipment. It is mainly used to opening(closing) load current, overload current and short-circuit current. It is suitable to protect or control the city or village electrical power distribution system.
Model No.: TD 12kv 1250A 25KA (JUC613) vacuum interrupter for VCB
Main technical parameters
Rated voltage: 12 KV
Rated current: 1250A
Rated power frequency withstand voltage: 42 KV
Rated lightning impulse withstand voltage: 75 KV
Rated short circuit breaking current: 25KA
Rated short circuit making current(peak value): 63KA
Breaking operations under rated short circuit breaking current: 30 times
Rated short time withstand current: 25KA
Rated withstand current(peak value): 63KA
Rated duration of short circuit: 4S
Mechanical life: 20,000 times
Closing force due to bellows and atmosphere: 120±50N
Force required to hold contacts opening at full stroke: 190±50N
Circuit resistance at lowest rated contacts force: �20μΩ
Storage life: 20 years
Limiting abrasion of contacts: 3 mm
Mechanical requiements of vacuum circuit breaker
Clearance between opening contacts: 11±1mm
Average opening speed(Contacts closing position~75% contacts opening distance): 1.1±0.2 m/s
Average closing speed(30% contacts opening distance~contacts closing position): 0.6±0.2 m/s
Rated contacts pressure: 2000±200N
Contacts bouncing duration at closing operation: â?¤2ms
Contacts re-bouncing clearance at opening operation: â?¤2mm
Synchronism of three phases: â?¤1ms
Items Value
Rated voltage 12KV
Rated current 1250A
Rated frequency 50Hz
Rated power frequency withstand voltage 42kV
Rated lightning impulse withstand voltage 75kV
Rated short circuit breaking current 25KA
Rated short circuit making current(peak value) 63KA
Breaking operations under rated short circuit breaking current 30 times
Rated short time withstand current 25kA
Rated withstand current(peak value) 63kA
Rated duration of short circuit 4s
Mechanical life 20000 times
Closing force due to bellows and atmosphere 120±50N
Force required to hold contacts opening at full stroke 190±50N
Circuit resistance at lowest rated contacts force �20μΩ
Storage life 20 years
Limiting abrasion of contacts 3mm
Â
Mechanical requiements of vacuum circuit breaker
Items Value
Clearance between opening contacts 11±1mm
Average opening speed(Contacts closing position~75% contacts opening distance) 1.1±0.2 m/s
Average closing speed(30% contacts opening distance~contacts closing position) 0.6±0.2 m/s
Rated contacts pressure 2000±200N
Contacts bouncing duration at closing operation â?¤2ms
Contacts re-bouncing clearance at opening operation â?¤2mm
Synchronism of three phases â?¤1ms
HVJ3 12KV VACUUM CONTACTOR
Detailed product description:
The vacuum contactor is mainly used in the power system with AC 50Hz and rated voltage 12kV, for making or breaking circuit and to make electromagnetic starter with suitable protective device and F-C switchgear.
Working condition:
1) Altitude should not be over 1,000m;
2) Ambient temperature: -5~40°C;
3) Average temperature in 24 hour not exceed 35°C;
4) When the highest temperature is 40°C, the relative humidity should not be higher than 50%;
5) Pollution degree: class 3
.Main models and technical parameters
Rated voltage: 12 KV
Control voltage: 220/110/380
Rated current: 160A, 250A, 400A, 630A
Clearance: 5±0.5 mm
Over travel: 2±0.2 mm
Pressure: >85N
Main circuit power frequency withstand voltage: 42000 v
Auxiliary circuit power frequency withstand voltage: 2500 v
Control circuit power frequency withstand voltage: 2000 v
Making capacity: 10Ie,100 times
Breaking capacity: 8Ie,25 times
Limit opening current(A): 10Ie
Overload: 8Ie,10 s
Mechanism life: 1 million times
Weight: 30KG
Note: â??Ieâ?? represents the rated current of main circuit
Model Rated voltage(v) Rated current
ï¼?Main circuitï¼?(A) Parameter of main contacts Power frequency
Withstand voltage
V(effective value)
Main
circuit Control
circuit Clearance
(mm) Over travel
(mm) pressure
(N)
Main
circuit Auxiliary
circuit Control
circuit
HVJ3-12/160 12000 220/110/380 160 5±0.5 2±0.2 >85N 42000 2500 2000
HVJ3-12/250 12000 220/110/380 250 5±0.5 2±0.2 >85N 42000 2500 2000
HVJ3-12/400 12000 220/110/380 400 5±0.5 2±0.2 >85N 42000 2500 2000
HVJ3-12/630 12000 220/110/380 630 5±0.5 2±0.2 >85N 42000 2500 2000
Â
Model Making capacity Breaking capacity Limit opening current(A) Overload Mechanism life Weight(kg)
HVJ3-12/160 10Ie,100times 8Ie,25times 10Ie 8Ie,10s 1million times 30
HVJ3-12/250 10Ie,100times 8Ie,25times 10Ie 8Ie,10s 1million times 30
HVJ3-12/400 10Ie,100times 8Ie,25times 10Ie 8Ie,10s 1million times 30
HVJ3-12/630 10Ie,100times 8Ie,25times 10Ie 8Ie,10s 1million times 30
Note: â??Ieâ?? represents the rated current of main circuit
1. General
The vacuum contactor is mainly used in the power system with AC 50Hz and rated voltage 7.2kV, for making or breaking circuit and to make electromagnetic starter with suitable protective device and F-C switchgear.
2. Working condition:
1) Altitude should not be over 1,000m;
2) Ambient temperature: -5~40°C;
3) Average temperature in 24 hour not exceed 35°C;
4) When the highest temperature is 40°C, the relative humidity should not be higher than 50%;
5) Pollution degree: class 3
Main models and technical parameters
Rated voltage: 7.2 kv
Control voltage: 380/220/110
Rated current: 630A
Clearance: 3.5±0.3 mm
Over travel: 2±0.2 mm
Pressure: >85N
Main circuit power frequency withstand voltage: 32000 v
Auxiliary circuit power frequency withstand voltage: 2500 v
Control circuit power frequency withstand voltage: 2000 v
Making capacity: 10Ie,100 times
Breaking capacity: 8Ie,25 times
Limit opening current(A): 10Ie
Overload: 8Ie,10 s
Mechanism life: 1 million times
Weight: 25.5 KG
Note: Ie represents the rated current of main circuit
1. General
The vacuum contactor is mainly used in the power system with AC 50Hz and rated voltage 7.2kV, for making or breaking circuit and to make electromagnetic starter with suitable protective device and F-C switchgear.
2. Working condition:
1) Altitude should not be over 1,000m;
2) Ambient temperature: -5~40°C;
3) Average temperature in 24 hour not exceed 35°C;
4) When the highest temperature is 40°C, the relative humidity should not be higher than 50%;
5) Pollution degree: class 3
Main models and technical parameters
Rated voltage: 7.2 kv
Control voltage: 380/220/110
Rated current: 630A
Clearance: 3.5±0.3 mm
Over travel: 2±0.2 mm
Pressure: >85N
Main circuit power frequency withstand voltage: 32000 v
Auxiliary circuit power frequency withstand voltage: 2500 v
Control circuit power frequency withstand voltage: 2000 v
Making capacity: 10Ie,100 times
Breaking capacity: 8Ie,25 times
Limit opening current(A): 10Ie
Overload: 8Ie,10 s
Mechanism life: 1 million times
Weight: 25.5 KG
Note: Ie represents the rated current of main circuit
1. General
The vacuum contactor is mainly used in the power system with AC 50Hz and rated voltage 7.2kV, for making or breaking circuit and to make electromagnetic starter with suitable protective device and F-C switchgear.
2. Working condition:
1) Altitude should not be over 1,000m;
2) Ambient temperature: -5~40°C;
3) Average temperature in 24 hour not exceed 35°C;
4) When the highest temperature is 40°C, the relative humidity should not be higher than 50%;
5) Pollution degree: class 3
Main models and technical parameters
Rated voltage: 7.2 kv
Control voltage: 380/220/110
Rated current: 160A
Clearance: 3.5±0.3 mm
Over travel: 2±0.2 mm
Pressure: >85N
Main circuit power frequency withstand voltage: 32000 v
Auxiliary circuit power frequency withstand voltage: 2500 v
Control circuit power frequency withstand voltage: 2000 v
Making capacity: 10Ie,100 times
Breaking capacity: 8Ie,25 times
Limit opening current(A): 10Ie
Overload: 8Ie,10 s
Mechanism life: 1 million times
Weight: 25.5 KG
Note: Ie represents the rated current of main circuit