Features
Troubleshoot real-time: Analyze the trends using the cursors and zoom tools-even while background recording continues.
Automatic Transient Mode: Capture 200 kHz waveform data on all phases simultaneously up to 6 kV
Measure all three phases and neutral: With included four current probes
System-Monitor: Up to ten power quality parameters on one screen according to EN50160 power quality standard
View graphs and generate reports: With included analysis software
Logger function: Configure for any test condition with memory for over 400 parameters at user defined intervals.
Mains signaling: Measure interference from ripple control signals at specific frequencies
Inrush mode: For troubleshooting nuisance circuit breaker tripping.
AutoTrend: Every measurement you see is always automatically recorded, without any setup.
Fully Class-A compliant: Conduct tests according to the stringent international IEC 61000-4-30 Class-A standard.
Battery Life: Seven hours operating time per charge on NiMH battery pack
High safety rating: 600 V CAT IV/1000 V CAT III rated for use at the service entrance
• Comparing to online power quality analyzer, E6000 handheld type with small size, light weight, easy for the engineer to carry and carry out to survey work whenever and wherever.
• Easy to wiring
• It can operate directly to the line under test under the circumstances that the Power Grid without interrupt.
• Multi-range current switching
• based on actual demand, the different range of current clamp can be replaced to improve measurement accuracy.
Applications
Frontline troubleshooting - quickly diagnose problems on-screen to get your operation back online
Predictive maintenance - detect and prevent power quality issues before they cause downtime
Quality of service compliance - validate incoming power quality at the service entrance
Long-term analysis - uncover hard-to-find or intermittent issues
Load studies - verify electrical system capacity before adding loads
Energy assessments - quantify energy consumption before and after improvements to justify energy saving devices.
Specifications
Measurement Items
Be measured Type of measurement
RMS Voltage Voltage
RMS Current Current
Frequency Deviation Frequency
Three-phase Unblanced Voltage, Current
Voltage fluctuations Voltage
Flicker Voltage
Harmonics and inter-harmonics, higher harmonic Voltage, current
Power Active, reactive, apparent power factor
Event log Transient pulse, the voltage rise, voltage sags, voltage interruption, the impact of current, frequency of abnormal
Input parameter
Measuring circuit 1P2W, 1P3W, 3P3W, 3P4W
The fundamental frequency of the measuring circuit 50Hz/60Hz
Number of input channels Voltage, current, 4
Measurement range Voltage Measurement Range: Nominal value: 100V, 230V, 400V, maximum 1000V
Current measurement range: Depending on the current clamp, current clamp the output voltage signal, the maximum voltage: 10V peak
Environmental security parameters
Use of the environment 0 ° C to +45 ° C, humidity 90rh%
Storage environment -20 ° C to +50 ° C, 95RH% humidity (non-condensing)
Power input voltage +100VAC ~ +240VAC
Electromagnetic Compatibility Level 3: GB / T 17626.2-2006 Electrostatic Discharge Immunity
Level 3: GB / T 17626.3-2006 RF electromagnetic radiation the Immunity
Level 3: GB / T 17626.4-2008 electrical fast transient burst immunity
Level3: GB / T 17626.5-2008 surge (impact) Immunity
Level 3: GB / T 17626.8-2006 frequency magnetic field immunity
Level 3: GB / T 17626.9-1998 Pulse magnetic field immunity
Level 3: GB / T 17626.12 -1998 Oscillatory waves immunity
Environmental reliability GB/T 2423.1-2008 low temperature
GB/T 2423.2-2008 high temperature
GB/T 2423.4-2008 alternating hot and humid
GB/T 2423.5-1995 impact
GB/T 2423.10-2008 vibration
GB/T 2423.22-2002 temperature changes
Dustproof, waterproof IP20(GB 4208-93/IEC 529:1989)
Security 500V/10M,2KV:GB/T 15479-1995
External interface parameters
USB Device 1 The upload power quality data
TF card to expand storage 1 Built-in capacity Optional, up to 8G
Battery 1 4500mAh Ni-MH battery
LCD 1 26 million color 5.6-inch LCD screen with a resolution of 640 * 480
Voltage and current measurement interface 8 Test voltage and current input port
Frequency
Measurement method 10 waveform (50Hz) the calculated frequency
Display Display of a channel frequency value
Measuring range / resolution 50.0000Hz/0.0001Hz
Measurement bandwidth 42.5000~57.5000Hz
Measurement accuracy ±0.001Hz
1/2 rms voltage 1/2 rms, current
Measurement method Once every two cycle operations, a waveform operations per cycle to take 1/2 cycle
Sampling Frequency 200K
Measuring range / resolution 120V/0.01,230V/0.01,400V/0.01,Based on the use of current clamp
Measurement accuracy 0.1% of the nominal voltage
RMS voltage
Measurement method 10 waveforms (50Hz) the operator
Display Per channel RMS voltage
Sampling Frequency 200K
Measuring range / resolution 120V/0.01,230V/0.01,400V/0.01
Measurement accuracy 0.1% of the nominal voltage
RMS voltage
Measurement method 10 waveforms (50Hz) the operator
Display Current per channel RMS
Sampling Frequency 200K
Measuring range / resolution Based on the use of current clamp
Measurement accuracy 0.1% of the nominal voltage
Harmonic voltage, harmonic current
Measurement method According to IEC61000-4-7, the magnitude of the analysis window 10 cycles
Window points Every 10 cycles of 5120 points
Display Histograms, tables
Sampling Frequency 200KHz
Number of measurements 0~50
Measuring range / resolution 120V/0.01,230V/0.01,400V/0.01
Measurement accuracy voltage harmonics greater than 1% of the nominal value: Error is less than 1% rdg
voltage harmonics less than 1% of the nominal value:Error is less than 0.05% rdg
the nominal voltage current harmonics greater than 3% of the nominal value: the error is less than 1% edg
current harmonics is less than 3% of the nominal value:Error is less than 0.05% of the nominal voltage
interharmonic voltage interharmonic current
Measurement method According to IEC61000-4-7, the magnitude of the analysis window 10 cycles
Window points Every 10 cycles of 5120 points
Display Form
Sampling Frequency 200KHz
Number of measurements 1~16
Measuring range / resolution 120V/0.01,230V/0.01,400V/0.01
Measurement accuracy voltage harmonics greater than 1% of the nominal value: Error is less than 1% rdg
voltage harmonics less than 1% of the nominal value:Error is less than 0.05% rdg
the nominal voltage current harmonics greater than 3% of the nominal value: the error is less than 1% edg
current harmonics is less than 3% of the nominal value:Error is less than 0.05% of the nominal voltage
High harmonic voltage, high harmonic currents
Measurement method Every 10 cycles of 5120 points
Window points Every 10 cycles of 5120 points
Display Form
Sampling Frequency 200KHz
Number of measurements 1 to 35 group
Measuring range / resolution 120V/0.01,230V/0.01,400V/0.01
Measurement accuracy voltage harmonics greater than 1% of the nominal value: Error is less than 1% rdg
voltage harmonics less than 1% of the nominal value:Error is less than 0.05% rdg
the nominal voltage current harmonics greater than 3% of the nominal value: the error is less than 1% edg
current harmonics is less than 3% of the nominal value:Error is less than 0.05% of the nominal voltage
Active power, reactive power, apparent power
Measurement method Active power: 10 cycles computing
Apparent power: Valid values of voltage and current operations
Reactive Power: apparent power, active power is calculated
Display Real-time data display
Sampling Frequency 200KHz
Measuring range / resolution Determined based on the voltage and current range
Measurement accuracy ±0.5%rdg
Power Factor
Measurement method Rms, current rms voltage, active power is calculated
Display Real-time data display
Sampling Frequency 200KHz
Measuring range / resolution -1.0000~1.0000
Measurement accuracy ±1%rdg
Voltage unbalance, current unbalance (negative and zero sequence)
Measurement method when 3-phase 3-wire or 3-phase 4-wire, calculate by three-phase fundamental ingredients
Display Voltage unbalance
current imbalance
Sampling Frequency 200KHz
Measuring range 0.00%~100%
Measurement accuracy Voltage unbalance: ± 0.5%
Current imbalance: ± 0.5%
Voltage fluctuations
Measurement method Half-wave to calculate the mean square
Display The fluctuation trends, real-time values of voltage fluctuation
Sampling Frequency 200KHz
Measuring range 0.00%~100%
Measurement accuracy ±1%
IEC Flicker
Measurement Item The short flicker (PST), long flicker (Plt)
Measurement method According to IEC61000-4-15 10 minutes PST continuous measurement, continuous measurement and calculation 2 hours Plt
Display The flicker trends, Pst value, Plt
Measuring range 0~20
Measurement accuracy ±5%
The impact of current
Measurement method Half-wave rms current exceeds the set value of the positive impact of current
Display The impact of current waveform, the impact of the current maximum
Measurement accuracy 0.10%
Measurement method Temporary swell: half-wave rms voltage positive direction exceeds a set value, it is determine as Temporary swell
temporary sag: Valid values are negative direction exceeds a set value, determine as temporary sag
Short interruptions: half-wave RMS voltage exceeds the set value in the negative direction, the decision for an instant interrupt
Display Temporary swell, sag, short interruptions waveform duration, amplitude etc.
Measurement accuracy 0.10%
Temporary swell, sag, short interruptions waveform duration, amplitude etc
Application
It is suitable for power department, measuring department, quality control department, research units, and institutions of higher learning, and electric energy meter, power distribution terminals, power supply management, load control, power quality, reactive power compensation device and production of the enterprise and so on.
Main Functions and Features
To set up and take the load regulation of voltage, current, phase and frequency of the power factor;
To be set to 2 ~ 128 times of the amplitude and phase harmonics, and it can be added to the base wave in every harmonic output;
Voltage, current output a wide range, big power, high stability, waveform distortion degree is very small;
To have strong with load ability, and take capacitive, sensibility, resistance of composite type load or load and load regulation is higher than 0.01% ;
To apply the 32 bit MPU + DSP + FPGA, powerful flexible;
To use hardware PID, fast response, the change of load will not cause output volatility;
Industrial frequency waves as high as 50000 points a week of the wave kneading, signal output without filter, precise output waveform, the harmonic output precision, harmonic distortion degree is small;
Range switching automatically;
To use software calibration, simple operation, stable and reliable;
To have the big screen, 320 x 240 LCD display, Chinese or English interface, operating simplely;
To have perfect over-current, over-voltage, heat, a shorts-and-opens, overload protection, automatic failure detection;
With RS232 interface, and PC connection;
To take place machine software, it can be output through the PC software of program.
Technical Data
AC voltage output
Range: 57.7 V / 100 V / 220 V / 380 V / 750 V, range switch automatically
Adjust fineness: 0.01% RG
Accuracy: RG is higher than 0.05%
Stability: better than 0.01% RG / 1 min
Distortion degree: better than 0.1% (not capacitive load)
Output power: the rated each phase is 40 VA
Full load regulation rate: less than 0.01% RG
Full load regulation time: less than 1mS
Temperature drift: 8 PPM / ¡æ
Long-term stability: 60 PPM/year
AC current output
Range: 0.1/0.25 A / 0.5/1 A / 5 A / 10 A / 20 A / 50 A / 100 A, range switch automatically
Adjust fineness: 0.01% RG
Accuracy: RG is higher than 0.05%
Stability: better than 0.01% RG / 1 min
Distortion degree: better than 0.1% (not capacitive load)
Output power: the rated each phase is 40 VA
Full load regulation rate: less than 0.01% RG
Full load regulation time: less than 1mS
Temperature drift: 8 PPM /
Long-term stability: 60 PPM/year
Phase angle
Adjusting range: 0 ~ 359.99
Resolution: 0.0
Accuracy: 0.03
Frequency
Adjusting range: 40 Hz ~ 65 Hz
Resolution: 0.001 Hz
Accuracy: 0.002 Hz
Temperature drift: 0.5 PPM /
Long-term stability: 4 PPM/year
Work power
Single phase AC 22015% , Frequency 50/60 Hz.
Volume and weight
Size: 420 mm x 320 mm x 155 mm (long x width ¡Á high)
weight: 12 kg
Environmental conditions
Working temperature: 0 ~ 40
Relative humidity: 85%
Storage conditions: -30
Product description
Gf102 single phase energy meter testing set used to test single phase energy meter. Adopt mature signal synthetic and power amplifier technology. High voltage and current output . Widely used in lab and field.
Features
Meter under testing: 1p2w
Testing mode: active power, reactive power
Test 3pcs or 2pcs meter synchronously
Starting test and creeping test
Reference standard and power source integrated, easy to carry.
Measuring mechanical meter and electric meter
Operating by manual keyboard or pc
With shortcut key of normal test point, speed up testing
Internal large capacity storage device for mass memory
Local checking the testing result
Overload, short circuit, open circuit protection
With self-checking function
Technical data
Voltage
Test voltage output (phase-neutral) 0v ¡v 264v
Power of the voltage output Max. 30va , 15va
Resolution 0.01%
Accuracy 0.1% , 0.2%
Stability 0.02%/120s , 0.05%/120s
Distortion factor < 0.3% for linear resistance load
Current
Test current output 1ma ¡v 120a , 1ma ¡v 60a
Power of the current output Max. 100va , 30va
Resolution 0.01%
Accuracy 0.1% , 0.2%
Stability 0.02%/120s
Distortion factor < 0.3% for linear resistance load
Phase angle
Range 0 -- 360¢x
Resolution 0.1¢x
Accuracy 0.2¢x
Frequency
Range 45hz ¡v 65hz
Resolution 0.005hz
Pulse output
High frequency output(ch) 1.666¡ñ105 hz
Low frequency output(cl) 5¡ñ10-5¡ñch
Pulse input
Input channel 3
Input frequency Max. 20hz
Other
Voltage supply 220v¡ó10% 50/60hz¡ó2hz
Ambient temperature -10¢xc -- +40¢xc
Relative humidity 35% -- 85%
Dimensions (w¡ñd¡ñh) (mm) 445¡ñ440¡ñ180 , 410¡ñ220¡ñ150
Weight (kg) 18 , 9.5
Dimensions (w¡ñd¡ñh) (mm) 445¡ñ440¡ñ180 , 410¡ñ220¡ñ150
Weight (kg) 18 , 9.5
1.Product description
Six-channel current output, six-channel voltage output, six-channel share of dc current, six-channel dc voltage output, eight pairs of binary input, four pairs of binary output.
2.Features
Integration in the host crystal 8.4 inches true color, light weight and easy to carry
Built-in high-speed high-performance industrial computer, embedded operating system, running a stable and reliable also be connected pc testing
Panel embedded user-friendly buttons can also be an external keyboard, mouse
High-precision dac to 12 road, simultaneous output to ensure that waveform fitting of high precision, good linearity
Matching electromagnetic compatibility components, can improve on-site anti-electromagnetic interference, protection devices can be connected electromagnetic compatibility tests
Analog output of the front panel, switch the amount of terminal design in the upper cover, all the wiring does not affect the operation of the panels and test parameters of the surveillance
Exterior appearance of cabinetImported electromagnetic compatible cabinet, which is made of high-grade all aluminum alloy extruded section and has fine appearance, is selected.
Dimension of cabinet: length¡ñwidth¡ñheight¡@360mm ¡ñ195mm ¡ñ365mm
Weight of cabinetWeight of host machine ¡@¡@¡@¡@¡@¡@¡@¡@¡@ ¡@16.6kg