1. General
HVD32 ZW32 This vacuum circuit breaker VCB is three-phase AC 50Hz, rated voltage 12 kV outdoor high voltage switch equipment. It is mainly used to opening(closing) load current, overload current and short-circuit current. It is suitable to protect or control the city or village electrical power distribution system.
2 . Main technical parameter
Rated voltage: 12 kv
1 minute rated power frequency withstand voltage: Phase to Phase, to Ground 42 kv / Fracture 48 kv
Rated current: 630A / 1250A
Rated short circuit breaking current: 12.5KA, 16KA, 20KA / 25KA
Rated short-circuit current (peak): 31.5KA, 40KA, 50KA / 63KA
Rated peak withstand current: 31.5KA, 40KA, 50KA / 63KA
4s rated short time withstand current: 12.5KA, 16KA, 20KA / 25KA
Rated operating sequence: O-0.3s-CO-180s-CO(Electric operation)
Closing time: 30-60 ms
Opening time: 20-40 ms
Rated short circuit breaking current breaking times: 30 times
Mechanical life: 10,000 times
Secondary circuit 1 minute power frequency withstand voltage: 2000 v
Energy storage motor rated power: 40 w
Energy storage motor rated voltage V: DC220/110
Rated closing operation voltage v: DC220/110, AC220/110
Rated switching operation voltage v: DC220/110, AC220/110
Electric energy storage time: =8 s
1. General VS1 12KV vacuum circuit breaker VCB HVD1-12(VS1-12) type indoor AC HV vacuum circuit breaker VCB (hereinafter referred to as circuit breaker) are suitable for 12kV air-insulated indoor switchgears, used as protection and control unit of power equipment of industrial& mining enterprise. Due to the super excellence, it is especially for location where requires the frequent operation of rated working current or multi breaking short circuit current. The circuit breaker adopts the integrated design of operating mechanism and circuit breaker body, servers as not only fixed installation, but also the handcart unit through equipping with a special propelling mechanism. 2. Service conditions 3.1 Environment temperature:-15degree~+40degree; 3.2 Environment humidity: Daily average relative humidity:
Vacuum Circuit Breaker VCB HVD32 12KV 630A VCB from Hubei JUCRO Electric 1.General HVD32 12KV This vacuum circuit breaker VCB is three-phase AC 50Hz, rated voltage 12 kV outdoor high voltage switch equipment. It is mainly used to opening(closing) load current, overload current and short-circuit current. It is suitable to protect or control the city or village electrical power distribution system.
VS1-12 type indoor high voltage vacuum circuit breaker is the indoor switch device for three-phase AC 50Hz, rated voltage 12kA power system, can be used for electrical equipment control and protection in power plant, substation and industrial and mining enterprises, and is suitable for frequent operation place, can be installed in the KYN28-12 type and other armored cabinet, can also be installed on the fixed cabinet or gas insulated cabinet. Design feature VS1-12kV indoor medium voltage sealed vacuum circuit breaker (12kV, .4000A, .50kA) VS1 indoor medium voltage sealed vacuum circuit breaker with maintenance free sealed vacuum pole, can equipped with modular spring assembling actuator and permanent magnetic actuator; has the features of reliable performance, long mechanical life, maintenance free, small mechanical movement, has the advantages of simple structure, good process performance, but also can be applied to all kinds of bad working environment. VS1 circuit breaker pole adapts the solid insulation sealing technology, seal the vacuum interrupter and primary main galvanic circle and other parts into strong insulation, high mechanical strength pole with epoxy resin, avoid the influence of adverse operating environment on the primary circuit external insulation, realizes completely maintenance free. VS1 circuit breaker adapt ultra low resistance type vacuum interrupter, meet the VCP circuit breaker requirements on the temperature rise at big current operation situation and reduces the power losses. VS1 circuit breaker adapt optimization and modular spring operating mechanism, simple structure, stable performance, convenient maintenance; modular production process is good, easy standardization production, short delivery cycle.
ZW32-24 type outdoor pole-mounted HV vacuum CB (hereinafter referred to as CB) is rated voltage24kV, 50Hz three-phase AC outdoor power distribution equipment used for power distribution network to break and close load current, over-load current and short-circuit current in electric systems. It is used in substation and industrial & mining enterprise power distribution system for protection and control, better fits countryside power grid and frequent operation places, especially for the retrofit of urban power network and countryside power network. Characteristic: The CB applies three-phase pole-type structure. It has characteristics of stable closing/breaking property, no fire or explosion danger, maintenance-free, small dimension, small weight, long service life, etc. The CB is hermetical sealed, and is moisture-resistant, anti-condensation. It is especially suitable for application at severe cold and damp areas. Three-phase pillar and current transformer apply imported outdoor epoxy resin solid insulation materials. It is high/low temperature resistant, UV-resistant and anti-ageing. The operating mechanism is miniature spring operating mechanism with low breaking/closing energy consumption. The driving of it applies straight transmission with little components and high reliability. The operating mechanism is enclosed in a cabinet, and that makes it rust-resistant and more reliable.
1.With the voltage of 40.5kV is three-phase AC, 50/60 Hz indoor power distribution equipment. 2.It is used for switchgear KYN61-40.5(Z) 3.It is accordance with GB1984 AC HV vacuum circuit breaker standard. 4.It effectively reduces the dimensions of VCB, the overall arrangement is reasonable and simple,with aesthetic appearance. 5.It has high reliable with characteristics of long life and easy maintenance and free-maintenance for operating mechanism. 6.Meet the Five Preventions function.
1.Use spring energy storage. 2.Operating by two ways: manual or electric operation 3.The characteristics is accordance with GB1984-2003 AC High Voltage Circuit Breakers, JB3855-96 3.6~40.5kV indoor AC HV vacuum circuit breaker, relevant regulations of IEC62271-100 standard and the technical requirements of this product. 4.Use modular type operating mechanism and embedded pole The mechanical life is M2 and electrical life is E2
1.General HVD85 ZN85 33kv 36KV indoor vacuum circuit breaker VCB is suitable for three-phase AC power system of 50Hz and 36kV, used to make and break the load current, overload current and fault current in industrial and mining enterprises, power plants and transformer substations, meanwhile, it is suitable for the occasion where the frequent operation is required. 2. Service conditions 2.1The ambient air temperature should be -15?~40?, the daily average temperature should not exceed 35?. 2.2 Daily mean relative humidity should not exceed 95%, and the daily mean vapor pressure should not exceed 2.2kPa; the monthly mean relative humidity should not be higher than 90%, and the monthly mean vapor pressure should not exceed 1.8kPa. 2.3 Altitude: Not exceed 1,000m. 2.4 The ambient air should be free from the dust, smoke, corrosive and flammable gas, steam, salt fog, et… Main specifications and technical parameters Rated voltage: 33KV 36kv Power frequency withstand voltage: 95 kv Lighting impulse withstand voltage: 185 kv Rated current: 1250A, 1600A, 2000A Rated short-time withstand current: 25KA, 31.5KA Rated peak value withstand current: 63KA, 80KA Rated short-circuit duration: 4 s Rated short-circuit breaking current: 25KA, 31.5KA Rated short-circuit making current: 63KA, 80KA Rated operation sequence: O-0.3s-CO-180s-CO Breaking time:
1. Introduction HVD7 33KV 36kv outdoor HV AC vacuum circuit breaker VCB has many visual advantages like reasonable design, fashionable appearance, high safety and reliability, simple maintenance, long electric life. It is the ideal upgraded products of 35KV outdoor oil circuit breakers. HVD7-40.5 vacuum circuit breaker is applicable for three-phase power system of AC 50HZ.It is used to make and break the load current ,overload current and short-circuit current. 2. Applicable environment 3.1The ambient temperature should be -30degree~ +40degree(-40degree in the frosty area); 3.2Altitude should not exceed 2000m(over 2000m is plateau type); 3.3The wind pressure should not exceed 700Pa(equal to wind speed 34m/s); 3.4Air pollution degree: 3,that of antifouling type:4; 3.5The installation site should be free from the fire, explosion, chemical corrosion and serious vibration. 1. Main technical parameters Rated voltage: 33kv 36KV 1 minute power frequency withstand voltage, dry test: 95 kv 1 minute power frequency withstand voltage, wet test: 80 kv Lightning impulse withstand voltage(peak value): 185 kv Rated current: 1600A / 2000A Rated short-circuit breaking current: 20KA, 25KA, 31.5KA Rated short-circuit making current(peak): 50KA, 63KA, 80KA Rated operating sequence: O-0.3s-CO-180s-CO Rated short-time withstand current: 20KA, 25KA, 31.5KA Rated peak withstand current: 50KA, 63KA, 80KA Rated short-circuit duration: 4 s Rated control voltage: AC220,110;DC220,110 Rated short-circuit breaking current break times: 20 times Full-break time: