EAC 30
Engine: CUMM NS
Engine Model : 4B3.9-G1
Stand By kVA: 30
Stand By kW : 24
Prime kVA: 27,2
Prime kW : 21,8
Rated Current : 39,2
Engine
- CUMM NS heavy duty diesel engine
- 12V starter and charge alternator
- Replaceable air, fuel and oil filters
- Mechanical governor control
- Tropical type radiator
- Flexible fuel hose
- Oil drain valve and extension hose
- Industrial type silencer and steel compensator
- Maintenance-free starter battery
- Water jacket heater
- 1500 rpm engine speed
Alternat
- IP 21-23 Protection Standard
- H Insulation Class
- 50 Hz Frequency
- 4 pole brushless synchronous type alternator
- Automatic Voltage Regulator (AVR)
- 400/230V AC Output Voltage - 1500 rpm
Sound Proof Canopy and Chassis
- Convenient design for easy lifting and carrying
- High standard sound proof canopy design
- Modular design with easily removable nuts - bolts
- Lockable doors
- Transparent window for watching Control Panel
- Electrostatic powder painted, providing protection against harsh weather conditions
- Emergency STOP button
- Fuel tank inside the chassis
- Anti-vibration wedges (engine - chassis and chassis â?? ground)
Optional
- Thermal magnetic CB (for automatic models)
- Super Silent Canopy
- Mobile Generator Sets
- Automatic fuel filling system
- Synchronization panel
- 3 Pole and 4 Pole ATS (Automatic Transfer Switch)
- Fuel Heater, Oil Heater
- External fuel tank and automatic fuel filling system
- Fuel - water separator filter
- Remote monitoring and control system
Engine CUMM NS
Engine Model 4B3.9-G1
Number of Cylinders 4 Inline
Injection System Direct
Compression Ratio 17.3: 1
Bore 102
Strok 120
Displacement L 3,9
Air Intake Natural Aspiration
Speed (RPM) 1500
Oil Capacity L 3,9
Standby Power kw / Hp 27 / 36
Prime Power Hp 24 / 32
Fuel Type Euro Diesel
Governor System Mechanical
Cooling System Water Cooling
Coolant Capacity L 8,3
Fuel Consumption (lt / h) L Full Load 7,1
L %75 LOAD 5,7
L %50 LOAD 4,3
Frequency Hz
Power kVA 30
Voltage V 230 / 400 V
Number of Phases 3
Automatic Voltage Regulator (A.V.R.) AS440
Voltage Regulation 1%
Insulation Class H
Protection Standard IP22-IP23
Power Factor 0,8
DIMENSIONS
Weight (Silent) Kg 880
Weight (Open) Kg 725
Width (Silent) Mm 900
Length (Silent) Mm 2200
Height (Silent) Mm 1350
Fuel Tank Capacity L 135
1 Standby Power : The max power available during a variable electrical power sequence, under the stated operating conditions, for which a generating set is capable of delivering in the event of a utility power outage. Overloading isn t permissible.
2 Prime Power : The maximum power which a generating set is capable of delivering continuously whilst supplying a variable electrical load. Average load should be 70%. The generator can be overloaded 10% for 1 hour per 12 hrs.