Supplier: Led bulb, tube light, panel light, decoration light, wall light, steel wires, steel plate, stainless steel plate, twisted wire rods, galvanized wires, wire mesh, site fencing, mosquito mesh, thread rods, rebar, twisted rods, t bar, nuts and bolts, hardware, pvc pipes, upvc pipes, api pipes, melamine, mdf board, plywood, film faced, shuttering, packing, core veneer, face veneer, hdf molded door skin, door filler, tubular particle boards, pvc boards, wpc boards, doors, block board, hard board, gypsum board, canopy, carpet, flooring wooden, bamboo, laminated engineering, tiles, granite tiles, granite blocks, black galaxy, wash basin, water closets, washbasins, ss sinks, faucets, furniture, pvc edge bending, crew, locks, pvc seals, silicone cartridges, shower enclosures, shower door hinges, handles, knobs, brackets, slides, nails, solar panels, flexible solar panels, solar power station, battery, inverters, rechargeable fans, lights, spring, 3ply disposable face mask, oxygen concentrator ,
Services: Buying office, oem, components sourcing, value added services
Buyer: In shell pecan nut, macadamia nut
Kecen KCM100/KC500 High Performance Vecter Variable Frequency Drive /Frequency Inverter / VFD/ AC drive (0.75KW-560KW /Output 3 Phase/ 220V/380V) for Motor /Fan pump / Water pumps /Blow molding machine/ Air condition / CNC/ Washing Machines/Transfer Machines/Crane/Blender/Spinning machine/Lathe/Papermaking machinery/Elevator/Stereo garage.
Product Structure 1. Bypass Cabinet (Optional) The by-pass cabinet or switching cabinet may employ isolating breaker, vacuum contactor or the combination, depending on the user¡¯s working conditions. The function of by-pass cabinet is to put the motor into operation in industry frequency grid after the WLD-HVF exits, so as to ensure the continuity of user¡¯s production. The switching cabinet is designed to divert the WLD-HVF output to different motors. 2. Transformer Cabinet Used for installation of Phase-shift transformer, it is dry type transformer with functions of temperature display and over-heat protection, also with insulation grade of H. The secondary multi-winding output provides phase-shift power supply to the power unit. This can greatly improve the current waveform on grid side and reduce the harmonic interference of the equipment to power grid lower of the National Criterion. 3. Power Unit Cabinet Used for installation of power units, which adopted imported high quality components inside, all power units are installed on the sliding seat, it is very easy to replace. 4. Control Cabinet Used for installation of low voltage control components, there are controller, PLC, UPS, Electric siren, DC 24V power supply, Control Power Source Switch, Wiring Terminals, Touch Screen, Operation Button etc. The equipment adopted fiber optical communications, which has a very good EMI restraining performance; The transformer, control cabinet and all power units, are built in temperature protection, so it will be maintenance free. Technical Features Voltage source High-high frequency inverter, it can realize No-step speed regulation, which makes the typical motors into intelligent motors. Low harmonics input and high power factor, the typical value for power factor is 0.95 through whole speed regulation, even more higher, no need for power factor compensation. WLD-HVF output few harmonics, the motor does not generate extra heat and noise. Modularized design of power units, interchangeable and easy to produce and repair, the equipment can find any fault exactly based on advanced diagnostic procedures in MPU. The inverter still can operate even the faults for part of power units exists, if there are faults happen for inverter, the system can switch to power frequency through bypass function. Applicable to all kinds of power grid at home and abroad and suitable for typical high voltage motor. Colorful touch screen, easy to operate and maintenance. Able to realize remote control, DCS operation and communications with Host, and support all kinds of communications interfaces such as CAN, Profibus, Modbus, RS232, RS485 etc. Applied latest components, master control chip adopted TI¡¯s DSP F28335 and ALTERA¡¯s FPGA of EP3C to realize powerful processing capacity; Sampling adopted AD¡¯s AD7606 with 16 bit to ensure control accuracy of the system. The switchgear can satisfy safety requirements, and the pressure-relief channel of high voltage switch can ensure safe use of operators. Technical Parameters Series No Parameters Value 1 HVF Capacity(KVA) 250~8750kVA 2 Power of adaptive motor(KW) 200~7000KW 3 Input Frequency(Hz) 45~65Hz 4 Harmonics contents injected to power grid 0.95%(>20% of rated load) 7 Efficiency >96%(under a rated load) 8 Output frequency(Hz) 0.5~120Hz 9 Precision of output frequency 0.01Hz 10 Rated output current(A) 36~600A 11 Overload capability 120%(1min), 150%(3s), 200%(Immediate protection) 12 Control mode V/F control or Vector control 13 Analog input 0~10V/4~20mA 14 Analog output 0~10V/4~20mA Optional (2 channels) 15 Boolean input/output Communications/Default point (expandable) 16 Acc & Dec time (S) 0.1~3000s 17 Altitude
Product Structure 1. Bypass Cabinet (Optional) The by-pass cabinet or switching cabinet may employ isolating breaker, vacuum contactor or the combination, depending on the user¡¯s working conditions. The function of by-pass cabinet is to put the motor into operation in industry frequency grid after the WLD-HVF exits, so as to ensure the continuity of user¡¯s production. The switching cabinet is designed to divert the WLD-HVF output to different motors. 2. Transformer Cabinet Used for installation of Phase-shift transformer, it is dry type transformer with functions of temperature display and over-heat protection, also with insulation grade of H. The secondary multi-winding output provides phase-shift power supply to the power unit. This can greatly improve the current waveform on grid side and reduce the harmonic interference of the equipment to power grid lower of the National Criterion. 3. Power Unit Cabinet Used for installation of power units, which adopted imported high quality components inside, all power units are installed on the sliding seat, it is very easy to replace. 4. Control Cabinet Used for installation of low voltage control components, there are controller, PLC, UPS, Electric siren, DC 24V power supply, Control Power Source Switch, Wiring Terminals, Touch Screen, Operation Button etc. The equipment adopted fiber optical communications, which has a very good EMI restraining performance; The transformer, control cabinet and all power units, are built in temperature protection, so it will be maintenance free. Technical Features Voltage source High-high frequency inverter, it can realize No-step speed regulation, which makes the typical motors into intelligent motors. Low harmonics input and high power factor, the typical value for power factor is 0.95 through whole speed regulation, even more higher, no need for power factor compensation. WLD-HVF output few harmonics, the motor does not generate extra heat and noise. Modularized design of power units, interchangeable and easy to produce and repair, the equipment can find any fault exactly based on advanced diagnostic procedures in MPU. The inverter still can operate even the faults for part of power units exists, if there are faults happen for inverter, the system can switch to power frequency through bypass function. Applicable to all kinds of power grid at home and abroad and suitable for typical high voltage motor. Colorful touch screen, easy to operate and maintenance. Able to realize remote control, DCS operation and communications with Host, and support all kinds of communications interfaces such as CAN, Profibus, Modbus, RS232, RS485 etc. Applied latest components, master control chip adopted TI¡¯s DSP F28335 and ALTERA¡¯s FPGA of EP3C to realize powerful processing capacity; Sampling adopted AD¡¯s AD7606 with 16 bit to ensure control accuracy of the system. The switchgear can satisfy safety requirements, and the pressure-relief channel of high voltage switch can ensure safe use of operators. Technical Parameters Series No Parameters Value 1 HVF Capacity(KVA) 250~8750kVA 2 Power of adaptive motor(KW) 200~7000KW 3 Input Frequency(Hz) 45~65Hz 4 Harmonics contents injected to power grid 0.95%(>20% of rated load) 7 Efficiency >96%(under a rated load) 8 Output frequency(Hz) 0.5~120Hz 9 Precision of output frequency 0.01Hz 10 Rated output current(A) 36~600A 11 Overload capability 120%(1min), 150%(3s), 200%(Immediate protection) 12 Control mode V/F control or Vector control 13 Analog input 0~10V/4~20mA 14 Analog output 0~10V/4~20mA Optional (2 channels) 15 Boolean input/output Communications/Default point (expandable) 16 Acc & Dec time (S) 0.1~3000s 17 Altitude
AC Drive. VFD (Variable Frequency Drive ) I Am A Distributors IN "KUNNAL" BRAND WE SUPLY TO BELLOW MODLE VFD 1 HP UPTO 100HP , ALL READIEST STOCK
Variable Frequency Drives
Supplier: Grains like corn, corn gluten meal, ddgs, soybeans, soybean meal, soy hull pellets, canola meal and pellets, cotton seeds and meal, and wheat, conventional or organic (non gmo), dairy products, frozen meats and seafood, plastic scraps, fish meal, fish oil, whey powder, flax seeds, beet pulp pellets, meat and bone meal, poultry meal, feed, 3d printers, beans, peas, nuts
Services: Commodities brokerage firm
Supplier: Rice, corn, sugar, wheat, cement, aluminum ingots, copper scrap , used rail and hms 1&2, urea, sulphur, cooking oils, petroleum products, aviation fuel, mazut, millet, alfalfa grass, timber logs, teak wood, wood pallet
Buyer: Steel scrap, used rails, cement