Catalyzed Oxygen Scavenger with polymers for
preventing pitting. Ideal for use with both hard and presoftened
make-up water.
Application
Can be injected directly into the boiler by means of a proportioning pump.
Advisable to gradually feed LC 102 by means of a chemical proportioning
pump into the storage section of the de-aerating heater as far ahead of
the boiler as possible to provide maximum effectiveness in high pressure
boiler operating from 100-600 psi. or where large amount of water is used.
Dosage
Initial : 3 quarts per 1,000 gallons or 3 : 4000
Maintenance: 1 quart for every 1,000 gallons of make-up water or 1 : 4000
Maintain 20-50 ppm (mg/l) in the boiler water. LC 102 can be used in
conjunction with other formula in our product line, but should not be used
in a boiler operating in excess of 600 psi.
Handling & Precaution
LC 102 is mildly acidic product and should be handled with care to prevent
personal injury. Wear protective clothing and eye protection. In case of
contact with skin, immediately flush with water. In case of contact with
eye, flush with water for 15 minutes and obtain immediate medical
attention.
Packaging
Available in pail of 20 lt.. Can also be custom packaged
Please ask detailed and specific