Catalyzed Oxygen Scavenger with polymers for preventing pitting. Ideal for use with both hard and presoftened make-up water. Application Can be injected directly into the boiler by means of a proportioning pump. Advisable to gradually feed LC 102 by means of a chemical proportioning pump into the storage section of the de-aerating heater as far ahead of the boiler as possible to provide maximum effectiveness in high pressure boiler operating from 100-600 psi. or where large amount of water is used. Dosage Initial : 3 quarts per 1,000 gallons or 3 : 4000 Maintenance: 1 quart for every 1,000 gallons of make-up water or 1 : 4000 Maintain 20-50 ppm (mg/l) in the boiler water. LC 102 can be used in conjunction with other formula in our product line, but should not be used in a boiler operating in excess of 600 psi. Handling & Precaution LC 102 is mildly acidic product and should be handled with care to prevent personal injury. Wear protective clothing and eye protection. In case of contact with skin, immediately flush with water. In case of contact with eye, flush with water for 15 minutes and obtain immediate medical attention. Packaging Available in pail of 20 lt.. Can also be custom packaged