HCJ3 7.2kv 630A vacuum interrupter for vacuum contactors 1. Brief introduction The interrupter adoption porcelain and ceramics makes to insulate the outer shell. Contact is WCCu metal alloy material advanced technique of adoption Including bulk small. Breaking the abiliting strong the life span is long maintenance is simple .no explosion dangerous no contaminate and the noise is low . The pack vacuum contactor can operate the ebery kind of electric appliances equipments, and fuse match f-c cabinet 2. Vacuum Tube main technique parameter Rated voltage: 7.2 kv Rated current: 630A Rated making current: 6.3KA Rated breaking current: 5.04KA Limiting breaking current: 6.3KA Rated short-time withstand current: 6.3KA Rated short-time withstand voltage: 32 kv Rated lighting impulse voltage: 60 kv Circuit resistance at lowest rated contacts force: =80µO Electrical life: 250,000 times Mechanical life: 500,000 times Closing force due to bellows and atmosphere: 70±20 N Force required to hold contacts open at full stroke: 100±30 N Limiting abrasion of contacts: 3 mm Internal gas pressure: =1.33×10-3 Pa Storage life: 20 years