Electrical Characteristics - Rated Voltage : 0.6/1 kV AC - Rated DC Voltage : 1.5 kV - Maximum Permitted DC Voltage : 1.8 kV (conductor/conductor, non earthen system, circuit not under load) - Maximum Permitted AC Voltage : 1 KV - Working Voltage : DC 1000 V - Spark Test : 6000 V. ac (8400 Vdc) - Voltage Withstand : 6500 V as per EN50395 for 5 min - Ampacity : According to requirements for cables for PV systems Technical Data - Ambient Temperature : -40C +90C - Minimum Bending Radius : 5 x OD (fixed), 15 x OD (occasional flexing) - Flame retardant according to IEC 60332-1-2 - Low smoke emission < 20% as per ASTM D-2843 - Halogen free according to EN 50267-2-1/-2, IEC 60754-2 - Maximum Temperature at Conductor : 120C (20000h) - Short Circuit Temperature : 200�?�°C (at conductor max. 5sec) - Thermal Endurance Test : According to EN 60216-2 (temperature index +120C) - High Temperature Pressure : Test according to EN 60811-3-1 - Excellent mechanical and electrical properties. - UV resistance & OZONE resistance - Flexibility & suitability for fast & easy installation Cable Standard EN 50618 Standard Packing Coils 100, 200,300, 500, 1000m Conductor Flexible Electrolytic fine Tinned copper class-5 conductor according to IEC 60228 Insulation XLPO (Crosslinked Halogen Free & Flame Retardant) Sheath XLPO (Crosslinked Halogen Free & Flame Retardant) Color Red, Black and also available black color with red lining. Application For Solar Panel, Solar Power Plant, Solar Pump Installation.