Overview
Frequency conversion series resonance test device is designed and manufactured for alternating-current withstand voltage test of Possessing a wider application scope, it is the ideal withstand voltage equipment for prefecture-level, municipal-level and county-level high-voltage test departements as well as power installation and repair & testing engineering units.
Frequency Conversion Series Resonance Test Device
Technical index
Rated voltage
Quality factor under full load in test of fire power generator Q 10 relating to load
Quality factor under full load in cable test Q 30 relating to load
Quality factor under full load in test of main transformer: Q 30 relating to load
GIS, the quality factor under full load in switch test and other tests Q 50 relating to load
Input power supply single phase of 380V
Frequency adjustment range 20Hz 300Hz
Accuracy of system measurement 1.5
The unit possesses protective functions, such as over voltage, over current and zero start.
Description for main configuration and technical data of equipment
One set of variable-frequency power supply
Rated power 10kVA;
Input voltage single phrase of 220V or three phase of 380V 10 and 45 65Hz
Output voltage 0 400V adjustable
Output voltage frequency 30 300Hz
0.1Hz adjustable stepping
Instability degree of frequency 0.02
Output current: 0 25A