Key features: Two independent differential pressure sensors Robust design, over-pressure protected Selectable pressure unit Signal output with possibility of spreading and inverting characteristic curve with any offset (optional) Characteristic conversion of output via 3, .30 entries tablets) Fully programmable via pc based eu03 module Large led display Key specifications: 1.Two independent differential pressure sensor. 2.Measuring range (of each sensor): 0 ~ 4.0 mbar up to 0 ~ 100 mbar; , ± 2.5 mbar to , ± 60.0 mbar 3.Maximum static operating pressure: 50 mbar to 500 mbar 4.Maximum safe pressure: 150 mbar to 1500 mbar 5.Straight line deviation error (max): 1.0% full scale 6.Pressure connection: g 1/8 female threads with optional cutting ring fittings for 6 or 8 mm tube 7.Operating ambient & media temperature: -10, ° c to +70, ° c 8.Protection class: ip65 per din en 60529 9.Electrical output: 4-20ma or 0-10v, 3 , ?? wire 10.Power supply: 24 v dc/ ac 11.Switching contacts: 2 sets of programmable voltage free contacts: no or nc 12.Display: 3 1/2 digit led 13.Electrical connections: two round shell multi-pin connector sockets (m12, male) 14.Material, housing: polyamide pa 6.6 15.Materials, media contact: silicon, pvc, aluminum, brass Application areas: 1.Roll band filter monitoring 2.Vacuum system monitoring 3.Chimney draught measurement 4.Flow and control pressure monitoring 5.Surface coating system 6.Pump monitoring and control 7.Compressor monitoring and control Industrial areas: 1.Air conditioning and ventilation systems 2.Auditorium, office, conference rooms 3.Hvac and ventilation application 4.Environment monitoring 5.Clean room and laboratory rooms