Model Flatpack2 380/3000 HE (UI)
Part number 241119.825
INPUT DATA
Voltage (nominal) 176 - 277 VAC / 260 - 400 VDC1)
Voltage (range) 85 - 305 VAC / 260 - 410 VDC1)
Frequency 45 - 66 Hz / 15 - 18.5 Hz2) / DC1)
Current (maximum) @ nominal input, full load 18.2 ARMS
Power Factor > 0.99 at 50% load or more
Protection
Fuse in L & N
Varistor
Disconnect when VIN is out of range
OUTPUT DATA
Voltage (default) 381 VDC
Voltage (adjustable range) 300 - 400 VDC
# Pb cell supported 156 - 168 3)
Power continuous (maximum) 3000 W
Power @ 85 VAC / 85 VDC 1200 W
Current continuous (maximum) 9 A (@VOUT < 336 VDC) / 7.9 A (@ VOUT = 381 VDC)
Current sharing (10 - 100% load) ±5% of maximum current from 10 to 100% load
Static Voltage regulation (10 - 100% load) ±0.5%
Dynamic Voltage regulation ±2.0% for 10-90% or 90-10% load variation, regulation time < 10 ms 5)
Hold up time > 20 ms; output voltage > 300 VDC at 1500 W load
Ripple < 1000 mVP-P , 30 MHz bandwidth
Protection Overvoltage shutdown, Hot plug-in - Inrush current limiting, ORing diode, Fuse5), Short
circuit proof, High temperature protection, Overload shutdown4)
OTHER SPECIFICATIONS
Efficiency @ 230 VAC / 380VDC input 96.2% / 96.6%
Isolation 3.0 kVAC input to output, 1.5 kVAC input to earth, 1.5 kVDC output to earth,
3.0 kVAC CAN to primary, 3.0 kVAC CAN to secondary
Alarms (Red LED) Low mains shutdown, High and low temperature shutdown, Rectifier Failure, Overvoltage
shutdown on output, Fan failure, Low voltage alarm, CAN bus failure
Warnings (Yellow LED) Rectifier in power derate mode, Remote battery current limit activated, Input voltage out
of range, flashing at overvoltage
Normal (Green LED) Input and output ok
Acoustic noise, at nominal input and full load < 40dBA @Tambient< 25C / 40C
MTBF (Telcordia SR-232 Iss.3 Meth. II Case L1) 2 291 210h (@ Tambient = 25 C)
Operating temperature -40 to +75C (-40 to +167F), humidity 5 - 95% RH non-condensing
Output power de-rates linear from 3000W @ 50C (122F) to 980W @ 7C(167F)
Storage temperature -40 to +85C (-40 to +185F), humidity 0 - 99% RH non-condensing
Dimensions[WxHxD] / Weight 109 x 41.5 x 327 mm (4.25 x 1.69 x 13) / < 1.95 kg (4.3 lbs)
DESIGN STANDARDS
Electrical safety EN 60950-1:2006+A11:2009+A1:2010+A12:2011+A2:2013, IEC 60950-1:2013, UL
60950-1:2014, CSA C22.2 No. 60950-1-07
EMC EN 61000-6-1:2007, -6-2:2005, -6-3:2007 + A1:2010, -6-4:2007 + A1:2010,
IEC61000-6-5: 2015, EN 300 386:v1.6.1, FCC CFR 47 Part 15:2013
Environment
Tested according to: ETSI EN 300 019: 2-1 (Class 1.2) & 2-2 (Class 2.3)
Normal operating conditions as per IEC 62040-5-3:2016 clause 4.2. Other operating
conditions as per IEC 62040-5-3:2016 clause 4.3, must be advised
2011/65/EU (RoHS) & 2012/19/EU (WEEE)