Scalable System 18-72 kVA, single input
MODEL 72 KW
Part number CTER3642.xxxx
INPUT DATA
Voltage range AC (3 phase Y) 320-475 V
Voltage range DC 40-58 V
Maximum current AC (per phase) 84-144 A
Frequency 50 Hz / 60 Hz
Power factor > 0.99
OUTPUT DATA
Adjustable range AC (3 phase Y) 346-415 V
Adjustable range DC 43-58 V
Max output power AC 54,0 kVA / 43,2 kW
Max output power DC 43,2 kW
Admissible load power factor 0 Ind. to 0 Cap.
Frequency 50 Hz / 60 Hz
Battery breaker (1-pole) 2*1600 or 4*600 A
OTHER SPECIFICATIONS
DC distribution 1 pole, 1-600 A
AC Distribution 1-3 pole 2-63 A
Manual Bypass Switch Internal
LVBD (1-pole) 1800 A
Eltek Micropack 48V/250W Rectifier
Micropack Wallbox
Power Supply System 12V/480W, 24V/960W or 48V/1000W
Compact wall-mounted power supply system
PRODUCT DESCRIPTION
The basic power core has 4 rectifier positions and can be configured as a bulk DC output feed, or integrated 1 or 2 pole distribution.
The power core is prepared for any Micropack rectifier module and the system output can be either of the following: (based on module
choice)
12V/120 480W / 10 40A
24V/240 960W / 10 40A
48V/250 1000W / 5.2 21A
The system has two options for monitoring and control, by the Compack controller, or if the display or extended controller functionality is needed it can be configured with Smartpack2 controller On the lower left side of the box there is space for optional backup batteries
(4x12V/7Ah, only with bulk DC output) .
A simple removable front cover gives good access for installation and connections.
47640 Electric Components Suppliers
Short on time? Let Electric Components sellers contact you.
PRODUCT DESCRIPTION
The basic power core has 4 rectifier positions and can be configured as a bulk DC output feed, or integrated 1 or 2 pole distribution.
The power core is prepared for any Micropack rectifier module and the system output can be either of the following: (based on module
choice)
12V/120 480W / 10 40A
24V/240 960W / 10 40A
48V/250 1000W / 5.2 21A
The system has two options for monitoring and control, by the Compack controller, or if the display or extended controller functionality is needed it can be configured with Smartpack2 controller On the lower left side of the box there is space for optional backup batteries
(4x12V/7Ah, only with bulk DC output) .
A simple removable front cover gives good access for installation and connections.
Power Supply System 12V/480W, 24V/960W, or 48V/1000W
Compact wall-mounted power supply system
Eltek Micropack wallbox has been designed for industrial and telecom applications with power requirements in the range of 120- 1000W. With its compact design and simple installation and optional
internal backup batteries make it a really â??microâ?? DC backup system.
Model Flatpack2 380/3000 HE (UI)
Part number 241119.825
INPUT DATA
Voltage (nominal) 176 - 277 VAC / 260 - 400 VDC1)
Voltage (range) 85 - 305 VAC / 260 - 410 VDC1)
Frequency 45 - 66 Hz / 15 - 18.5 Hz2) / DC1)
Current (maximum) @ nominal input, full load 18.2 ARMS
Power Factor > 0.99 at 50% load or more
Protection
Fuse in L & N
Varistor
Disconnect when VIN is out of range
OUTPUT DATA
Voltage (default) 381 VDC
Voltage (adjustable range) 300 - 400 VDC
# Pb cell supported 156 - 168 3)
Power continuous (maximum) 3000 W
Power @ 85 VAC / 85 VDC 1200 W
Current continuous (maximum) 9 A (@VOUT < 336 VDC) / 7.9 A (@ VOUT = 381 VDC)
Current sharing (10 - 100% load) ±5% of maximum current from 10 to 100% load
Static Voltage regulation (10 - 100% load) ±0.5%
Dynamic Voltage regulation ±2.0% for 10-90% or 90-10% load variation, regulation time < 10 ms 5)
Hold up time > 20 ms; output voltage > 300 VDC at 1500 W load
Ripple < 1000 mVP-P , 30 MHz bandwidth
Protection Overvoltage shutdown, Hot plug-in - Inrush current limiting, ORing diode, Fuse5), Short
circuit proof, High temperature protection, Overload shutdown4)
OTHER SPECIFICATIONS
Efficiency @ 230 VAC / 380VDC input 96.2% / 96.6%
Isolation 3.0 kVAC input to output, 1.5 kVAC input to earth, 1.5 kVDC output to earth,
3.0 kVAC CAN to primary, 3.0 kVAC CAN to secondary
Alarms (Red LED) Low mains shutdown, High and low temperature shutdown, Rectifier Failure, Overvoltage
shutdown on output, Fan failure, Low voltage alarm, CAN bus failure
Warnings (Yellow LED) Rectifier in power derate mode, Remote battery current limit activated, Input voltage out
of range, flashing at overvoltage
Normal (Green LED) Input and output ok
Acoustic noise, at nominal input and full load < 40dBA @Tambient< 25C / 40C
MTBF (Telcordia SR-232 Iss.3 Meth. II Case L1) 2 291 210h (@ Tambient = 25 C)
Operating temperature -40 to +75C (-40 to +167F), humidity 5 - 95% RH non-condensing
Output power de-rates linear from 3000W @ 50C (122F) to 980W @ 7C(167F)
Storage temperature -40 to +85C (-40 to +185F), humidity 0 - 99% RH non-condensing
Dimensions[WxHxD] / Weight 109 x 41.5 x 327 mm (4.25 x 1.69 x 13) / < 1.95 kg (4.3 lbs)
DESIGN STANDARDS
Electrical safety EN 60950-1:2006+A11:2009+A1:2010+A12:2011+A2:2013, IEC 60950-1:2013, UL
60950-1:2014, CSA C22.2 No. 60950-1-07
EMC EN 61000-6-1:2007, -6-2:2005, -6-3:2007 + A1:2010, -6-4:2007 + A1:2010,
IEC61000-6-5: 2015, EN 300 386:v1.6.1, FCC CFR 47 Part 15:2013
Environment
Tested according to: ETSI EN 300 019: 2-1 (Class 1.2) & 2-2 (Class 2.3)
Normal operating conditions as per IEC 62040-5-3:2016 clause 4.2. Other operating
conditions as per IEC 62040-5-3:2016 clause 4.3, must be advised
2011/65/EU (RoHS) & 2012/19/EU (WEEE)