ier output, rectifier bridge with snubber protection, short check of functions and times, option to program the equalized charge automatically, lab tested electronic circuit conforming to the directive on electromagnetic compatibility and CE marking, automatic Start, automatic disconnection of battery charger due to battery disconnection, equalization charge based on time, charging with decreasing current (Wa characteristic): 9÷11 h charging time, transformer thermal protection, modular installation on galvanized steel base (20/10) – (30/10), sheet steel case with modular panels (10/10 - 12/10) - (12/10 – 15/10), epoxy powder coating, oven-baked, standard colour: RAL 2002 red, option: custom-made colour, logo and silk-screen printing, mains input and d.c. output polarized cables, complete with mains and battery cables; assembly of plugs and battery connectors on request. “WA” CHARACTERISTIC (DIN 41774): charge at decreasing current with intervention of the final charge at 2.40 V/cell., final charge with timed control 9h / 11h, fixed charging time (equalization charge excluded), equalization charge (week-end charge) to be recalled. It will start after 55’ from charge end, duration of equalized charging phase: each hour 5’ (repeated for 48 hours), calculation to determine the size of suitable battery charge: 16A for every 100 Ah of the battery (e.g. 500 Ah battery: 16Ax5 = 80A).