1. Introduction
JCZ5 12kv vacuum contactor
HVJ6-12 series indoor high-voltage AC vacuum contactor has two types: One is Mechanical holding type, the other is Electromagnetic holding type. It is applicable for three-phase AC 50HZ power system of rated voltage 12KV and below and rated current up to 630 A to open and close circuit remotely and control electrical equipment like high-voltage motor, transformer and capacitive load. It is especially suitable for fields operated frequently. The contactor uses the international fashionable up and down structure arrangement and has the advantages of small, light, easy to maintain and form a complete set of circuit equipment.
2. Service condition
a) Ambient air temperature: -25- +40.
b) Altitude not exceed 2000m
c)Humidity:
-Relative humidity: daily mean not higher than 95,monthly mean not higher than 90;
-Aqueous vapor pressure: daily mean not exceed 2.2 KP, monthly mean not exceed 1.8 KP
Ambient air should not be obviously polluted by corrosive or flammable gas or vapor;
C)Free of frequent severe vibration; When running, angle of inclination between installation surface and horizontal plane should not exceed 5.
Main technical parameters
Rated voltage: 12000 v
Control circuit: 110V 220V
Rated current: 200A 400A 630A
Contacts separation: 5+1-0.5 mm
Over travel: 1.5±0.5 mm
Main circuit power frequency withstand voltage: 42000 v
Auxiliary circuit power frequency voltage withstand: 2500 v
Control circuit power frequency voltage withstand: 2000 V
Making capacity: 10le,100 times
Breaking capacity: 8le, 25 times
Limit breaking current(A): 10le
Mechanical life times: 30104
Weight: 32KG
JCZR 7.2kv 12kv Indoor Vacuum Contactor-Fuse Combination Electric Appliance General: This combination electric appliance may install in the switch cabinet to form the F-C loop, use with the integrated protection device. It is used for loading of the switching on and switching off the power pant as well as the industry and mining enterprise, dropout AC high-tension motor, the transformer, capacitor and so on, and it has overload, short circuit protection function. This combination electric appliance may use in AC 50 HZ three-phase power systems. Technical Data: 1. Main Technical Parameter see Table 1. Rated voltage: 7.2 kv / 12 kv Power frequency withstand voltage phase to phase, to earth: 32 kv / 42 kv Power frequency withstand voltage the fracture impact withstand voltage(fracture): 60 kv / 75 kv Fuse rated current A: 25-250 / 25-250 Prospective short circuit breaking current KA: 50 / 50 Prospective short circuit making current(peak value) KA: 130 / 130 Prospective short circuit withstand current( peak value) KA: 10 / 10 Rated short time withstand current( effective value) KA: 4 / 4 Rated short circuit duration S: 4 / 4 Rated making current KA: 4 / 4 Rated breaking current KA: 3.2 / 3.2 Limit breaking current KA: 4.5 / 4.5 Contactor distance between fixed and moving contact mm: 4.5 / 5 Contactor over-travel mm: 1.5 / 1.5 Mechanical life times: Model J:100,000; Model D:300,000 / Model J:100,000; Model D:300,000 Closing coil Rated operation voltage(V): DC220,DC110 Opening coil Rated operation voltage(V): DC220,DC110 Holding coil Rated operation voltage(V): DC220,DC110 Closing coil power: 1200 W Holding coil power: 15 W Opening coil power: 80 W Closing coil Normal work voltage range: 85%-110% rated voltage Holding coil Normal work voltage range: 85%-110% rated voltage Opening coil Normal work voltage range: 60%-120% rated voltage
1. General The vacuum contactor is mainly used in the power system with AC 50Hz and rated voltage 7.2kV, for making or breaking circuit and to make electromagnetic starter with suitable protective device and F-C switchgear. 2. Working condition: 1) Altitude should not be over 1,000m; 2) Ambient temperature: -5~40°C; 3) Average temperature in 24 hour not exceed 35°C; 4) When the highest temperature is 40°C, the relative humidity should not be higher than 50%; 5) Pollution degree: class 3 Main models and technical parameters Rated voltage: 7.2 kv Control voltage: 380/220/110 Rated current: 630A Clearance: 3.5±0.3 mm Over travel: 2±0.2 mm Pressure: >85N Main circuit power frequency withstand voltage: 32000 v Auxiliary circuit power frequency withstand voltage: 2500 v Control circuit power frequency withstand voltage: 2000 v Making capacity: 10Ie,100 times Breaking capacity: 8Ie,25 times Limit opening current(A): 10Ie Overload: 8Ie,10 s Mechanism life: 1 million times Weight: 25.5 KG Note: Ie represents the rated current of main circuit
Supplier: Branded consumer electronics, televisions, cameras, home appliances, car audio systems, hair curlers, hair trimmers, hair clippers, hair straighteners, beard trimmers, shavers, vacuum cleaners, air purifiers, blenders, mixers, juicers etc, mg3710/15 mg3730/15 mg5720/15 mg7720/15 bt1233/14 bt3206/14 bt3216/14
HVJ3 12KV VACUUM CONTACTOR Detailed product description: The vacuum contactor is mainly used in the power system with AC 50Hz and rated voltage 12kV, for making or breaking circuit and to make electromagnetic starter with suitable protective device and F-C switchgear. Working condition: 1) Altitude should not be over 1,000m; 2) Ambient temperature: -5~40°C; 3) Average temperature in 24 hour not exceed 35°C; 4) When the highest temperature is 40°C, the relative humidity should not be higher than 50%; 5) Pollution degree: class 3 .Main models and technical parameters Rated voltage: 12 KV Control voltage: 220/110/380 Rated current: 160A, 250A, 400A, 630A Clearance: 5±0.5 mm Over travel: 2±0.2 mm Pressure: >85N Main circuit power frequency withstand voltage: 42000 v Auxiliary circuit power frequency withstand voltage: 2500 v Control circuit power frequency withstand voltage: 2000 v Making capacity: 10Ie,100 times Breaking capacity: 8Ie,25 times Limit opening current(A): 10Ie Overload: 8Ie,10 s Mechanism life: 1 million times Weight: 30KG Note: “Ie” represents the rated current of main circuit
1. Introduction JCZ5 7.2 kv vacuum contactor HVJ6-7.2 series indoor high-voltage AC vacuum contactor has two types: One is Mechanical holding type, the other is Electromagnetic holding type. It is applicable for three-phase AC 50HZ power system of rated voltage 7.2KV and below and rated current up to 630 A to open and close circuit remotely and control electrical equipment like high-voltage motor, transformer and capacitive load. It is especially suitable for fields operated frequently. The contactor uses the international fashionable up and down structure arrangement and has the advantages of small, light, easy to maintain and form a complete set of F-C circuit equipment. 2. Service condition a) Ambient air temperature: -25?- +40?. b) Altitude not exceed 2000m c)Humidity: -Relative humidity: daily mean not higher than 95?,monthly mean not higher than 90?; -Aqueous vapor pressure: daily mean not exceed 2.2 KP, monthly mean not exceed 1.8 KP Ambient air should not be obviously polluted by corrosive or flammable gas or vapor; C)Free of frequent severe vibration; When running, angle of inclination between installation surface and horizontal plane should not exceed 5?. Main technical parameters Rated voltage: 7.2 kv Control voltage: 110V, 220V Rated current: 200A, 400A, 630A Contacts separation: 4.5+1-0.5mm Over travel: 1.5±0.5 mm Main circuit power frequency voltage withstand: 32000 V Auxiliary circuit power frequency withstand voltage: 2500 V Control circuit power frequency withstand voltage: 2000 V Making capacity: 10le,100 times Breaking capacity: 8le, 25 times Limit breaking current(A): 10le Mechanical life times: 30×104 Weight: 28KG
Supplier: Woven/knit and non woven fabric and its relative products like disposable medical products, home/hotel textiles, essential oils, household appliances, kitchenware, fiberglass mesh cloth, etc.