Product Details
3.1 Key Specifications/Special Features
Function Rated input voltage * Relay output Model
Phase sequence and
phase loss monitoring 3-phase, 3-wire 220 to 440 VAC Relay: 1 NC,1 NO TVR-2000B
3-phase, 3-wire 380 to 660 VAC Relay: 1 NC,1 NO TVR-2000C
* The power supply voltage is the same as the rated input voltage.
Ratings
Rated input voltage 3-phase, 200 to 440 VAC (3-wire)
Input load Approx. 2.6 VA
Operating
time Phase
sequence 1 s±0.05 s
Phase loss 0.1 s max.
(when the voltage changes rapidly from 100% to 0% of rated voltage)
Indicators LED Normal: Green light; phase loss: Red light; Inverted: Yellow light
Output form Relay Output: SPDT contact
Output relay ratings Rated load
Resistive load
5 A at 250 VAC
5 A at 30 VDC
Maximum switching capacity: 1,250 VA, 150 W
Minimum load: 5 VDC, 10 mA (reference values)
Mechanical life: 10 million operations min.
Electrical life:
5 A at 250 VAC or 30 VDC:50,000 operations
3 A at 250 VAC/30 VDC:100,000 operations
Ambient operating
temperature -20 to 60°C (with no condensation or icing)
Storage temperature -25 to 65°C (with no condensation or icing)
Ambient operating
humidity 25% to 85% RH (with no condensation)
Storage humidity 25% to 85% RH (with no condensation)
Altitude 2,000 m max.
Applicable wires Stranded wires, solid wires, or ferrules
Applicable wire size 0.25 to 1.5 mm2 (AWG24 to AWG16)
Wire insertion force 8 N max. for AWG20 wire
Screwdriver
insertion force 15 N max.
Wire stripping length 8 mm
Ferrule length 8 mm
Current capacity 10 A (per pole)
Number of
insertions 50 times
Weight Approx.55g
Mounting Mounts to DIN Track, or screw mounting
Dimensions 30 Ã? 60 Ã?70 mm (WÃ?DÃ?H)
Specifications
Input frequency
range 50 to 60 Hz
Phase loss detection
level 80%±10% of rated input Calculation Formula
= 1 â?? ((Highest phase-to-phase voltage â?? Lowest phase-to-phase voltage)/
Average three-phase phase-to-phase voltage)
Applicable
standards Conforming
standards EN 60947-5-1
Installation environment (pollution level 2, Overvoltage category III)
EMC EN 60947-5-1
Insulation resistance 20 MΩ min.
Between external terminals and case
Between input terminals and output terminals
Dielectric strength 2,000 VAC for one minute
Between external terminals and case
Between input terminals and output terminals
Impulse withstand
voltage 6 kV (between live terminals and exposed, non-charged metal parts)
Vibration resistance Frequency: 10 to 55 Hz, 0.35-mm single amplitude
10 sweeps of 5 min each in X,Y, and Z directions
Shock resistance 100 m/s2, 3 times each in 6 directions along 3 axes
Degree of protection Terminals: IP20
-
Fnad Electrical Appliance Plant, established is located in Ningbo, China. It is 2km away from Geely Automobile Industrial Park. It is a science and technology enterprise integrating with R&D, manufacture, trade and service. The Plant has focused on motor protection for more than years. It is specialized in applications of single-chip microcomputer technology in the fields of industrial control, power electronics and automobile electronics. Our main products include motor protectors, phase failure protectors, phase sequence protectors, volt-ammeters, surge protector, temperature controllers, etc. we have an in-depth study in prevention of occurrence of phase failure, phase sequence, overload, under-load, overvoltage, under-voltage, three-phase imbalance, over-current and similar abnormalities in customersâ?? equipments and provide such solutions as prevention, alarming and equipment protection. It supports major elevator plants, thermal power plants, automobile plants, crane factories, textile mills, refrigerating plants and chemical plants and provides solutions for them. Some products have passed CE certification and ROSH environmental certification of European Union. We endeavor to make the company to be listed in Hong Kong in 2020. Welcome to visit and communicate with us. -
Fnad Electrical Appliance Plant, established is located in Ningbo, China. It is 2km away from Geely Automobile Industrial Park. It is a science and technology enterprise integrating with R&D, manufacture, trade and service. The Plant has focused on motor protection for more than years. It is specialized in applications of single-chip microcomputer technology in the fields of industrial control, power electronics and automobile electronics. Our main products include motor protectors, phase failure protectors, phase sequence protectors, volt-ammeters, surge protector, temperature controllers, etc. we have an in-depth study in prevention of occurrence of phase failure, phase sequence, overload, under-load, overvoltage, under-voltage, three-phase imbalance, over-current and similar abnormalities in customersâ?? equipments and provide such solutions as prevention, alarming and equipment protection. It supports major elevator plants, thermal power plants, automobile plants, crane factories, textile mills, refrigerating plants and chemical plants and provides solutions for them. Some products have passed CE certification and ROSH environmental certification of European Union. We endeavor to make the company to be listed in Hong Kong in 2020. Welcome to visit and communicate with us. -
Key Specifications/Special Features Ratings Power supply voltage Power consumption 24 VAC/DC: 1.8 VA/1 W max. 100 to 240 VAC: 2.5 VA max. Rated insulation voltage 600 VAC Operating value setting range (SV) 10% to 100% of maximum setting range Operating value 100% operation at set value Reset value setting range (HYS) 5% to 50% of operating value Reset method Note:Manual reset: Turn OFF power supply for 1 s or longer. Operating time setting range (T) 3to8 s Indicators Normal : Green light; Overvoltage Undervoltage : Yellow light Output form one Normally open and one normally closed Output relay ratings Rated load 5 A at 250 VAC (Resistive load) 5 A at 30 VDC (Resistive load) 1 A at 250 VAC (Inductive load) 0.2 A at 48 VDC (Inductive load) Minimum load: 5 VDC, 10 mA (reference values) Mechanical life: 10 million operations min. Electrical life: 5 A at 250 VAC or 30 VDC: 50,000 operations 3 A at 250 VAC or 30 VDC: 100,000 operations Ambient operating temperature -20 to 60°C (with no condensation or icing) Storage temperature -25 to 65°C (with no condensation or icing) Ambient operating humidity 25% to 85% RH (with no condensation) Storage humidity 25% to 85% RH (with no condensation) Altitude 2,000 m max. Applicable wires Stranded wires, solid wires, or ferrules Applicable wire size 0.25 to 1.5 mm2(AWG24 to AWG16) Wire insertion force 8 N max. for AWG20 wire Screwdriver insertion force 15 N max. Wire stripping length 8 mm Ferrule length 8 mm Current capacity 10 A (per pole) Weight Approx. 60 g Mounting Mounts to DIN Track Dimensions 30 � 60 �76 mm (W�H�D) Specifications Conforming standards EN 60947-5-1 Installation environment (pollution level 2, Overvoltage category III) Insulation resistance 20 MΩmin. Between external terminals and case Between power supply terminals and input terminals Between power supply terminals and output terminals Between input terminals and output terminals Dielectric strength 2,000 VAC for one minute Between external terminals and case Between power supply terminals and input terminals Between power supply terminals and output terminals Between input terminals and output terminals Impulse withstand voltage 6 kV (between live terminals and exposed, non-charged metal parts) Vibration resistance Frequency: 10 to 55 Hz, 0.35-mm single amplitude 10 sweeps of 5 min each in X,Y, and Z directions Shock resistance 100 m/s2, 3 times each in 6 directions along 3 axes Degree of protection Terminals: IP20 -
SANDI SERIES charging module is for electric vehicle charging station. With single-phase non neutral conductor AC input, it has the advantages of high efficiency, high power density and low harmonic. Functional details 1. Hot plug Plug technology is applied to the charging module to provide convenience for installation and maintenance. The access of the charging module to the system shall not disturb the output voltage of the system. 2. Advanced current sharing technology Under constant voltage working mode, the charging modules can share current automatically within 10S, with degree of unbalance less than �±0.5A. 3. Control of input limited power Refer to Fig. 1-10 for the relation between the output power and input voltage of the charging module. When the input voltage is within 360 Vac ~ 450 Vac (return difference is less than 5V), the module can output the maximum power of 20 KW; when the input voltage is within 260 Vac ~ 320 Vac, the module can still work normally under limited power mode. 4. Control of output constant power When there is a rated input voltage, the output power of the module is 20 KW. Refer to Fig. 11 for the relation between the output voltage and the output current of the module. The SD75050 module uses two operating modes with output voltage ranges of 50 to 750V. The module only selects the operating mode based on the value of the received demand voltage, and does not select the operating mode based on the actual output voltage. 5. Temperature limited power 6. Regulation of output current limiting point 8. Regulation of output voltage The output voltage of the module can be regulated constantly through the external monitoring module, with regulation range of 50Vdc ~ 750Vdc and minimum regulation step of 0.1 Vdc. 9. Fan control The built-in processor of the module can regulate the speed of the fan according to the internal temperature and output current of the module. 10. Protection of input overvoltage/ voltage shortage 11. Output overvoltage protection The overvoltage protection point is 260Vdc ~770Vdc (�±10 Vdc). Default is 778Vdc.The module can be started after manual intervention upon overvoltage protection. 12. Over-temperature protection The environmental over-temperature protection point is 80�°C. When the DC panel has a temperature over 100�°C, the module will stop working; when the DC panel has a temperature below 90�°C, the module will automatically work again. 13. Protection of internal bus fault When the internal bus voltage of the module is beyond the overvoltage/ voltage shortage protection point, the module will be powered off automatically. At this time, there is no output from the module and the fault indicator light is on. 14. Short circuit protection In case of short circuit of the module, it will be subjected to protective shutdown and the red indicator light of the panel is on, and this condition will be transmitted to the monitor of the "module fault".
Field Failure Relay (FFR) For D.C. Drives and Instrumentation The Field Failure Relay, when used in series with the field circuit, ensures that no power is supplied to the Armature unless Field circuit is complete. Field Failure Relay, also known as Field Loss Relay protects the D.C. Shunt motor or main circuit under open field conditions. Welcome to Insel Rectifiers: Your Premier Destination for Field Failure Relays At Insel Rectifiers, we take immense pride in being recognized as the forefront manufacturer and supplier of Field Failure Relays. Our commitment revolves around providing cutting-edge solutions that guarantee the reliability and efficiency of your systems. With a trusted legacy in the industry, we excel in the art of meticulously crafting precision-engineered Field Failure Relays and Field Loss Relays. Our dedication sets the benchmark for quality and innovation, ensuring your systems operate seamlessly and meet the highest standards of performance. Precision in Field Failure Relay Manufacturing At Insel Rectifiers, we take pride in our meticulous approach to manufacturing Field Failure Relays. These relays play a critical role in safeguarding your systems against unforeseen failures, and our commitment to precision engineering ensures that each relay meets the highest industry standards. As a distinguished Field Failure Relay manufacturer, we understand the importance of reliability in your operations. Efficient Solutions for Field Loss Relays Insel Rectifiers is your go-to source for efficient Field Loss Relay solutions. Our relay products are designed to detect and respond to field failures promptly, minimizing downtime and ensuring the seamless operation of your systems. As your dedicated Field Loss Relay supplier, we prioritize innovation to deliver cutting-edge solutions tailored to meet the unique needs of your applications. Innovative Technology, Trusted Supplier Insel Rectifiers is not just a manufacturer; we are your trusted partner in reliable relay solutions. Our commitment to innovation is reflected in the advanced technology embedded in our Field Failure Relays. As a leading Field Loss Relay supplier, we understand the importance of providing products that not only meet but exceed customer expectations. Why Choose Insel Rectifiers? Quality Assurance: Rigorous testing procedures ensure the reliability and durability of our Field Failure Relays. Innovation: We continually invest in research and development to bring you the latest advancements in relay technology. Customer Satisfaction: At Insel Rectifiers, your satisfaction is our priority. Our dedicated support team is ready to assist you with any inquiries or technical assistance.
AC to DC converter battery charger 150-1000VDC rectifier 120KW power supply Product Introductionï¼? SANDI AC/DC Charger is specially developed for DC chargers. It has high efficiency, high power factor, high power density, high reliability advantage. AC input 3 phase, DC output voltage range from 150 to 1000VDC can be set, compliant with CE safety requirements, EMC standard EN61000-6-3 and EN61000-6-1 Class A, it is an advanced international level charger. Unique function High efficiency over the full load range, full load efficiency greater than 95% Wide output voltage range, 150-1000VDC, suitable for a wide range of Lithium or lead acid battery 5-inch LCD touch screen, easy to operate Flexible application, charging voltage, charging current, charging time, timing charging can be set by LCD screen, easy to operate Main featuresï¼? Powerful protection, overheating, short circuit, overload, overvoltage, undervoltage, etc. Wide input voltage range: 260~ 530Vac, adaptable to various power grid environments Three-phase AC input without neutral wire: Simplifies system design, eliminates the risk of excessive neutral current, and reduces system costs. Dual DSP design, achieve the full digital control, less components means high reliability Wide input voltage range, allows operation in most poor grid conditions Battery anti backflow: effectively protects the battery while ensuring reliable and safe operation of the system Input, output have protective circuit breaker switch Module adopts hot pluggable design, which is convenient for maintenance. RS485 interface (Optional)