In the instruments industry, the traditional 4 20 mA analog transmitters are upgrading to the fieldbus with digital communication. HART fieldbus communication has digital communication capability with compatible analog signal. HART MODEM is a necessary and convenient tool for the analog products upgrading and signal exchanging in the control plant. We provide two kinds of HART modem. HART-RS232 is the converter for HART signal to RS-232 signal. HART-USB is the converter for HART signal to PC virtual series port.
Product characteristic:
According to the HART physical layer specification
Isolated transformer prevents the influence of earthing.
Voltage signal modulator/demodulator
Low power consumption designation
Powered by series port or USB port
Interface Type: DB9 female mount
Ambient Temperature: 0 ~ 50 °C
Compressive Strength :500 V AC HART bus and serial port (UART,USB)
Receiving Impedance : �5 K Ω, end-to-end
Output Signal VPP: 600 mV � VPP � 400 mV, 500 Ω load resistance
Receiving Sensitivity: 120 mV, 500 Ω test resistance
HART-RS232 is the protocol converter between HART device and configurator on PC.
The figure above is a sample basic case. To connect multiple HART device, please connect the other devices parallel with the Transmiter. Please note that the power should support multiple devices and the terminator should be set in the middle of the power and parallel point.
HART-RS232 is a HART MODEM with voltage modulator/demodulator. To communicate with a HART device, please connect the clincher of HART port of HART-RS232 to the two terminals of the network adaptor resistance or the power of HART device. To communicate with a PC, please connect the other port of HART-RS232 to the series port of PC.
The USB driver installation program should be run for HART-USB. The driver provides a virtual series ports for HART configurator software.
The indication light shows the state of modem. Green LED indicates the power is working well and the modem is sending data. Red LED indicates the modem is receiving data
Product Overview
G1003 gateway realizes protocol converting from HART to Modbus RTU / ASCII. Supporting to connect multi HART slave devices into Modbus network. In the gateway, HART terminal is master station, Modbus terminal is slave station.
Features
Be tallied with HART7.0
HART master and Modbus slave mode
4~20mA analog signal overlay HART digital signal
Support 15 HART slave device
Configure gateway by special software
Write protect user data
RS485 Modbus interface
LED power and communication indicating
Standard DIN rail installation
Product Overview
M0313 module makes it possible to convert Modbus RTU protocol directly to FF H1 protocol. Using M0313 module, the difficulty of development can be reduced and the upgrade of Modbus RTU device can be easily achieved. Only by simply configuration, the users can realize conversion from Modbus RTU protocol to FF protocol. M0313 module is provided with two LED indicating lights, used to indicate the current working status.
Features
Support 1 Modbus RTU slave device
1 RES function block complying to FF specification
1 Modbus transducer block
4 PID function blocks complying to FF specification
4 for each AI,AO,DI,DO function block complying to FF specification, each function block supports 8 channels
Modbus RTU device upgrading
LED working status indicator
G1013 HART to FF Gateway, designed by Microcyber Corporation is a gateway device for HART protocol and FF protocol. As HART master, G1013 HART to FF Gateway communicates with HART slave via HART interface, it can convert dynamic variables in the device to FF device variables output.
Product Description
Provide FF H1 communication ability to HART device
Support standard DD or EDD specification (FF H1)
Electrical interface connected with HART device
Supports FSK(1200bps)
G1013 HART to FF Gateway is 99Ã?22.5Ã?114.5mm, supporting standard DIN rail installation.
G1013 HART to FF Gateway is powered by FF bus, and the HART part shall be with 24V external powered. The recommended is TP cable, and it shall improve devices anti-electromagnetic interference ability.
Physical Parameters
Bus signal: compliant with IEC61158-2 physical layer standard
Bus power supply: 9 ~ 32V
Operating temperature: -40 ~ 85°C
Static current: â?¤14mA
Humidity range: 5% ~ 95%,non-dew
Mechanism size: diameter 66mm(can be customized)
Supportive MODBUS Communication Parameters
Address: 1 ~ 255
Baud rate: 9600 / 19200 / 15625 / 31250 /62500 / 125000 bps
Data bit: 7 / 8 bits
Calibration: odd / even calibration
Stop bit: 1 / 2 bits
CRC calibration: low byte ahead / high byte ahead
Data format: support various data formats
Supportive MODBUS Function Code
Function Code 1: read loop status
Function Code 2: read discrete input status
Function Code 3: read keeping register value
Function Code 4: read input register value
Function Code 6: write loop
Function Code 16:write multiple register values
Product Overview
M0310 module makes it possible to convert Modbus RTU protocol directly to HART protocol. Using M0310 module, the difficulty of development can be reduced and the upgrade of Modbus RTU device can be easily achieved. Only by simply configuration, the users can realize conversion from Modbus RTU protocol to HART protocol. M0310 module is provided with two LED indicating lights, used to indicate the current working status.
Features
Comply with HART PROTOCOL standard V7.0
HART slave station and Modbus master station form
Support 1 Modbus RTU slave device
Support 6 device variables,4 dynamic variables
Configured by HART interface
Write-protection of users data
Support high/low current transfinite alarm
TTL Modbus interface
LED power and communication indicator
Modbus-DP built-in module realizes the connection from Modbus RTU device to PROFIBUS DP network .It realizes the conversion function from MODBUS Protocol to PROFIBUS DP Protocol. Only by simply operating Modbus configuration tool, the users can realize connection from Modbus RTU device to PROFIBUS DP network.
M0306 module works with DIP16 2.54mm standard interface, 3.3 V power supply, Modbus communication indicating light to quick diagnosis the device status. It uses simple convenience
Combining with the features of high reliability and high flexibility, M0306 module is an ideal choice for user to develop OEM devices with PROFIBUS DP protocol.
MODBUS-RTU master station, comply with MODBUS-RTU protocol
Electrical interface connected with Modbus device supports TTL level
Set MODBUS-RTU slave station via parameters provided by GSD file
Company Information
Microcybers production center is 1700m2, with anti-static ground, ventilating system, air source transporting system, temperature and humility control system and production devices. The production center consists of 4 workshops and 1 professional lab, they are: production workshop, assembly workshop, ageing workshop, maintenance workshop and product lab. There are professional production line, pressure transmitter assembly line, instrument assembly line, control system module assembly line and product testing line. Microcyber has the batch capacity for 10 thousand devices per year.
Provide FF H1 communication ability to Modbus device
Support standard DD or EDD specification (FF H1)
Electrical interface connected with Modbus device
supports TTL level, RS485 and RS232
G0313 Modbus to FF Gateway is a gateway device of Modbus protocol and FF protocol developed by Microcyber. As Modbus master station, G0313 Modbus to FF Gateway communicates with Modbus-RTU device via RS485 interface, and it can convert the data of Modbus-RTU device to FF device variable output.
G0313 Modbus to FF Gateway size is 99Ã?22.5Ã?114.5mm, and supports standard DIN rail installation.
There is a 3-bit DIP switch for G0313 Modbus to FF Gateway, shown as the following Figure.
SIM: Simulation switch, used for simulation function.
WP: Write protection, all the write operation for FF smart pressure transmitter shall be refused, which avoid data modification at random.
RST: Reset, reset device date to factory original. Power off the device at first, and made the switch at ON, and then power on the device, the device shall be reset to factory original.
Modbus to FF gateway is a gateway device supporting Modbus and FF protocol. As FF device, it can communicate with Modbus devices, read Modbus data to FF device by simply configuration, and transfer data to control system through FF bus.
Modbus to FF Gateway supports 4 Modbus slave devices, 8 groups of analog input output and discrete input output parameters, totally 32 channels provided. It configures Modbus devices data into transducer blocks parameters via Modbus register, and provides data support for FF system via channels between variables and AI, AO, DI and DO function blocks.
Physical Parameters
Bus signal: compliant with IEC61158-2 physical layer standard
Bus power supply: 9 ~ 32V
Operating temperature: -40 ~ 85°C
Static current: â?¤14mA
Humidity range: 5% ~ 95%,non-dew
Mechanism size: diameter 66mm(can be customized)
Supportive MODBUS Communication Parameters
Address: 1 ~ 255
Baud rate: 9600 / 19200 / 15625 / 31250 /62500 / 125000 bps
Data bit: 7 / 8 bits
Calibration: odd / even calibration
Stop bit: 1 / 2 bits
CRC calibration: low byte ahead / high byte ahead
Data format: support various data formats
Supportive MODBUS Function Code
Function Code 1: read loop status
Function Code 2: read discrete input status
Function Code 3: read keeping register value
Function Code 4: read input register value
Function Code 6: write loop
Function Code 16:write multiple register values
NCS-PT105 series Smart Pressure Transmitter with advanced, mature, reliable 3151 capacitance sensors has been designed meticulously by combining advanced microprocessor technology and digital capacitance measurement technology. The powerful functions and high-speed computing capability of the microprocessor make it have excellent qualifications such as smart, high precision, high reliability, stable zero and so on. Its LCD can display many physical parameters (e.g. pressure, temperature, current and so on). It can realize the functions such as zero adjustment, range settings by key-press operation, and it is easy for field testing.
NCS-PT105 series Smart Pressure Transmitter supports HART, FF, and PA protocol and can measure pressure, differential pressure, liquid level, flow, and other industrial parameters. It can be widely used in the petroleum, chemicals, electricity, and metallurgical industries, etc..
According to the type of measurable pressure:
Model Pressure type
NCS-PT105 SR Micro-differential pressure transmitter
NCS-PT105 SG Gauge pressure transmitter
NCS-PT105 SA Absolute pressure transmitter
NCS-PT105 SD Differential pressure transmitter
NCS-PT105 SH Differential pressure transmitter for high static pressure
According to the protocol:
Model Communication Protocol type
NCS-PT105 H HART
NCS-PT105 F FF H1
NCS-PT105 P PROFIBUS PA
As a transitional communication protocol in fieldbus, HART protocol achieves digital transmission on the existing analog transmission lines, and is compatible with existing analog signal control system. Either FF H1or PROFIBUS PA is a new generation of digital communication protocol, used in field connection, and linking field devices. International Standard IEC61158-2 is used in physical layer. Therefore, either FF H1or PROFIBUS PA is fieldbus actually.
As following, Smart Transmitter with HART protocol is named as HART Smart Transmitter; Smart Transmitter with FF H1 protocol is named as FF Smart Transmitter; Smart Transmitter with PROFIBUS PA protocol is named as PA Smart Transmitter, All of these (Transmitters with the three types of fieldbus protocol) are named as Smart Pressure Transmitters or Smart Transmitters. In addition, HART Smart Transmitter has passed explosion-proof certification from National Supervision and Inspection Center for Explosion Protection and Safety of Instrumentation (NEPSI).
Product Overview
NCS-PT105IIS series Smart Pressure Transmitter with advanced, mature, reliable Piezoresistive Silicon Sensors has been designed meticulously by combining advanced microprocessor technology and digital capacitance measurement techniques. The powerful functions and high-speed computing capability of the microprocessor make it have excellent qualifications such as intelligent, high-precision, high reliability, stable zero and so on. Its LCD can display many physical parameters such as pressure, temperature, current. It can be realized zero adjustment, range settings and other features by key-press operation, and easy to on-site tests.
NCS-PT105IIS series Smart Pressure Transmitter supports HART, FF H1, Profibus PA, Profibus DP protocol and can measure pressure, differential pressure, liquid level, flow, and other industrial parameters. It can be widely used in the petroleum, chemicals, electricity, and metallurgical industries, etc.
Features
Performance up to 0.075% of accuracy
Gauge pressure, absolute pressure
Automatically environmental temperature compensation
Parameters can be set by magnetic sticks, communicator, HOST software
Measurement media: liquid, gas and stream
HART®, FOUNDATIONâ?¢ Fieldbus, PROFIBUS®
Up to ±0.1% of Upper Range Limit (URL) for 1 year
NCS-TT108 smart temperature transmitter, using the fieldbus technology, is a new generation of smart fieldbus temperature transmitter and it is an indispensable field device for process control. NCS-TT108 transmitter integrates abundant function blocks and realizes not only general measurement function but also complicated control strategy.
NCS-TT108 smart temperature transmitter supports eight-channel temperature sensor input. It applied to a variety of thermal resistance and thermocouple sensors and has wide range. Each channel support individually configure the sensor type and two-wire system and three-wire system connections of the thermal resistance. Eight channels are divided into four groups of temperature acquisition modules, with the security isolation between modules. Each temperature acquisition module has two temperature input channels.
NCS-TT108 smart temperature transmitter adopt PVC fire-retardant plastic shell, which can be installed in the control room. When it is required to be installed outdoors, outdoor Aluminum box, with a water-proof body and die-cast aluminum materials, must be selected.
NCS-TT108 uses digital technology. It has simple interface between field and control room, which reduces the expense of installation, operation and maintenance.
NCS-TT108 supports FF, and PA protocols. It can be widely used in the petroleum, chemicals, electricity, and metallurgical industries, etc.
Main features:
nflexibility
------Support many types of thermal resistance and thermocouple sensors
-------Thermal resistance supports 2/3 wiring connection mode
------Thermocouple can use cold end compensation function
nSupport many type of protocols
-----Support FF, PA protocols
1.Modbus-RTU protocol to HART protocol
2.Support 6 device variables and 4 dynamic variables
3.Support Modbus communication parameters dynamic configuration
4.Support HART multipoint mode
5.Support 375/475 communicator
Product Overview
NCS-TT106 smart temperature module, using the fieldbus technology, is a new generation of smart fieldbus temperature transmitter and it is an indispensable field device for process control.
Features
Support multiple thermal resistance and thermocouples
Thermal resistance supports 2/3/4-wire connection mode
Thermocouple can use cold end compensation function
Better accuracy: PT100 ±0.3 ; K-type ±0.4
Universally programmable for various input signals
Available protocols: HART /FF H1 /PROFIBUS PA
Parameter
Value
Input Signal
Resistance: PT100, CU50, CU100, 0~500Ω, 0~4000Ω
Thermocouple: B, E, J, N, K, R, S, T
Voltage signal: -100mV~100mV
Channel Single
RTD Wiring 2-wire, 3-wire, 4-wire
Bus Power 9~32 VDC Current consumption (static): â?¤14mA
Bus Signal Communication ratio 31.25Kbit/s, current mode
Isolation Between terminal and housing: 1kV
Working Temperature -40~85
Humidity Range 10%~90%RH
Start Time â?¤5s
Refresh Time 0.5s
EMC GB/T 18268-2000
Protection IP20
Signal Type Suggested Range ()
Accuracy
Resistance 0~500Ω,0~4000Ω ±0.05%
PT100 -200 ~ 850 ±0.2
PT1000 -200~ 850 ±0.1
CU50 -50 ~ 150 ±0.3
CU100 -50 ~ 150 ±0.2
mV -100mV ~ 100mV 0.05%
B 500 ~ 1810 ±1.0
E -200 ~ 1000 ±0.4
J -190 ~ 1200 ±0.4
K -200 ~ 1372 ±0.4
N -190 ~ 1300 ±0.8
R 0 ~ 1768 ±1.0
S 0 ~ 1768 ±1.0
T -200 ~ 400 ±0.4
NCS Series of Intelligent Transmitters are digital, intelligent, network-based, merged with advanced, reliable and stable sensor technology, to be designed as a new generation of Fieldbus Intelligent Transmitter.
NCS Series of Intelligent Transmitter have been designed with high precision and high reliability, high stability. The pressure, temperature, currents and other physical quantities are displayed on LCD module. Zero drift, range settings and many other functions, are realized by the magnetism bar operation. The interoperability between different systems and equipments are realized by the Equipment Description Document, which is compatible to a variety of device management software, and adapting to harsh electromagnetic environment. NCS Series of Intelligent Transmitter have been used in inflammable and explosive places according to Intrinsically Safety Design.
The Fieldbus Technology is used in NCS-TT105 Intelligent Temperature Transmitter, which is a new generation of Fieldbus Intelligent Temperature Transmitter, also an indispensable field device in control processing. It is integrated with a variety of functional modules, to realize not only the general testing functions, also the complicated control strategy.
Digital technology is applied in NCS-TT105, which has been used in a wide range of thermal resistance and thermocouple sensors. It has a wide measuring range. Because of the simple interface between the field and control room, the costs of installation, operation and maintenance are reduced a lot.
NCS-TT105 Series of Intelligent Temperature Transmitters, complied with FF Protocol, have been widely used in petroleum, chemical, metallurgy, electricity, cement,etc.
Thermo resistance additional parameters as follows:
Parameter
Function Description
COMP_WIRE1
Linearization compensation for thermo resistance 1 selecting 2-wire or 3-wire.
Unit is fixed as Ω.
COMP_WIRE2
Linearization compensation for thermo resistance 2 selecting 2-wire or 3-wire.
Unit is fixed as Ω.
SENSOR_CONNECTION
It can be used to connect sensor with 2-wire or 3-wire.
0: 2-wire
1: 3-wire
NCS-TT108 smart temperature transmitter, using the fieldbus technology, is a new generation of smart fieldbus temperature transmitter and it is an indispensable field device for process control. NCS-TT108 transmitter integrates abundant function blocks and realizes not only general measurement function but also complicated control strategy.
NCS-TT108 smart temperature transmitter supports eight-channel temperature sensor input. It applied to a variety of thermal resistance and thermocouple sensors and has wide range. Each channel support individually configure the sensor type and two-wire system and three-wire system connections of the thermal resistance. Eight channels are divided into four groups of temperature acquisition modules, with the security isolation between modules. Each temperature acquisition module has two temperature input channels.
NCS-TT108 smart temperature transmitter adopt PVC fire-retardant plastic shell, which can be installed in the control room. When it is required to be installed outdoors, outdoor Aluminum box, with a water-proof body and die-cast aluminum materials, must be selected.
NCS-TT108 uses digital technology. It has simple interface between field and control room, which reduces the expense of installation, operation and maintenance.
NCS-TT108 supports FF, and PA protocols. It can be widely used in the petroleum, chemicals, electricity, and metallurgical industries, etc.
Main features:
nflexibility
------Support many types of thermal resistance and thermocouple sensors
-------Thermal resistance supports 2/3 wiring connection mode
------Thermocouple can use cold end compensation function
nSupport many type of protocols
-----Support FF, PA protocols
G1013 HART to FF Gateway, designed by Microcyber Corporation is a gateway device for HART protocol and FF protocol. As HART master, G1013 HART to FF Gateway communicates with HART slave via HART interface, it can convert dynamic variables in the device to FF device variables output.
Product Description
Provide FF H1 communication ability to HART device
Support standard DD or EDD specification (FF H1)
Electrical interface connected with HART device
Supports FSK(1200bps)
G1013 HART to FF Gateway is 9922.5114.5mm, supporting standard DIN rail installation.
G1013 HART to FF Gateway is powered by FF bus, and the HART part shall be with 24V external powered. The recommended is TP cable, and it shall improve devices anti-electromagnetic interference ability.