SNA-360 analogue addressable photoelectric smoke/heat detectors are microprocessor controlled state-of-the-art
Detectors compatible with popular control and indicating equipment loop protocols.
Advanced electronics in conjunction with a photoelectric smoke sensing chamber and an electronic thermistor provide
Early detection of fire and high immunity against unwanted alarms. The heat sensor provides sensitive rate-of-rise
Operation or fixed-temperature operation when the response threshold value is exceeded.
Photoelectric smoke and heat sensors
Analogue detection discrimination
Dual leds for 360° visibility
Dc 24 v operation
2-wire connection to many popular loop protocols
Dip switch address setting
125 usable detector address settings per loop
Optional remote led output
The 6001 analogue addressable control and indicating equipment forms the central part of a fire detection and alarm
System. The fully networkable 2-wire 6001 is compatible with numens addressable devices and can also be
Connected to non-addressable devices when used with addressable input modules.
Default configuration programming facilitates out-of-box installation and rapid commissioning. A powerful and versatile
Cause-and-effect pc-based programming tool enables rapid customization with software for sites that require
Special operating features.
The 6001 comes standard with features that allows flexibility and expandability.
Single loop or 2-loop options available
Single loop, expandable to 2-loops available
Networkable, up to 4 control panels
Up to 125 addressable devices per loop
Automatic device detection on start-up
Automatic device type-code verification
2 independently programmable non-addressable a/v alarm output circuits
2 programmable fire alarm relay outputs
Fault relay output
Backlit lcd display providing 4 rows of 40 characters
16 zone fire alarm led indicators
3000 event history log
SNC-300 non-addressable photoelectric smoke detectors are state-of-the-art detectors suitable for connection to
2-wire or 4-wire non-addressable fire detection control and indicating equipment, or to addressable fire detection
Control and indicating equipment that can accept non-addressable type detectors.
Advanced electronics in conjunction with a photoelectric smoke sensing chamber provide early detection of fire
And high immunity against unwanted alarms.
Photoelectric smoke sensor
Analogue detection discrimination
Dual leds for 360° visibility
2-wire and 4-wire models for dc 12 v and dc 24 v operation
4-wire model for dc 48 v operation
4-wire models available with a n/o alarm relay output
4-wire models available with auto-reset
2-wire models available with remote led output
Connects to zone monitor for use with addressable control and indicating equipment
HNC-310 non-addressable heat detectors are suitable for connection to 2-wire non-addressable fire detection control
And indicating equipment, or to addressable fire detection control and indicating equipment that can accept
Non-addressable type detectors.
An electronic thermistor provides sensitive rate-of-rise operation or fixed-temperature operation when the response
Threshold value is exceeded.
Durable heat sensor
Analogue detection discrimination
Dual leds for 360° visibility
2-wire and 4-wire models for dc 12 v and dc 24 v operation
Dual leds for 360° visibility
4-wire models available with a n/o alarm relay output
4-wire models available with auto-reset
2-wire models available with remote led output
Connects to zone monitor for use with addressable control and indicating equipment
The 660 manual call points includes a pressure-activated displacement element to provide a safe and convenient
Way for building occupants to manually initiate a fire alarm condition.
Resetting the manual call point is achieved by inserting a key through the underside of the unit to replace the
Operating face to the quiescent position.
Pressure activated displacement element provides a safe user experience
Integral indicator to show polling and alarm activation
Resettable with simple key operation
Suitable for indoor use
Monitors for quiescent, alarm and fault conditions
Dip switch address setting
125 usable detector address settings per loop
The 640 addressable audio/visual alarm devices are suitable for connection to 2-wire addressable fire detection
And alarm systems.
640 is loop-powered and activation is initiated by a dedicated initiation message from the control and indicating
Equipment. Up to 125 devices can be connected to each alarm zone loop.
Visual, audible and audio/visual models available
Red or white body available for audible alarm device
Loop-powered from control and indicating equipment
Operates when a dedicated activation message is received from the control and indicating equipment
Loud sounder output of 85 db at 1 m
Long-life leds
Low quiescent current
Dip switch address setting
The 640 addressable audio/visual alarm devices are suitable for connection to 2-wire addressable fire detection
And alarm systems.
640 is loop-powered and activation is initiated by a dedicated initiation message from the control and indicating
Equipment. Up to 125 devices can be connected to each alarm zone loop.
Visual, audible and audio/visual models available
Red or white body available for audible alarm device
Loop-powered from control and indicating equipment
Operates when a dedicated activation message is received from the control and indicating equipment
Loud sounder output of 85 db at 1 m
Long-life leds
Low quiescent current
Dip switch address setting
Snc-300 non-addressable photoelectric smoke/heat detectors are state-of-the-art detectors suitable for connection
To 2-wire or 4-wire non-addressable fire detection control and indicating equipment, or to addressable fire detection
Control and indicating equipment that can accept non-addressable type detectors.
Advanced electronics in conjunction with a photoelectric smoke sensing chamber and an electronic thermistor
Provide early detection of fire and high immunity against unwanted alarms. The heat sensor provides sensitive
Rate-of-rise operation or fixed-temperature operation when the response threshold value is exceeded.
Photoelectric smoke and heat sensors
Analogue detection discrimination
Dual leds for 360° visibility
2-wire and 4-wire models for dc 12 v and dc 24 v operation
4-wire model for dc 48 v operation
4-wire models available with a n/o alarm relay output
4-wire models available with auto-reset
2-wire models available with remote led output
Connects to zone monitor for use with addressable control and indicating equipment
The 460 manual call points includes a pressure-activated displacement element to provide a safe and convenient
Way for building occupants to manually initiate a fire alarm condition.
Resetting the manual call point is achieved by inserting a key through the underside of the unit to replace the
Operating face to the quiescent position.
Pressure activated displacement element provides a safe user experience
Integral indicator to show polling and alarm activation
Resettable with simple key operation
Suitable for indoor use
Monitors for quiescent, alarm and fault conditions
The 442 audio/visual alarm devices are suitable for connection to 2-wire and 4-wire fire detection and alarm
Systems.
441 will operate with both addressable and non-addressable fire detection control and indicating equipment.
Activation is initiated upon connection of the operating voltage, allowing connection to either a switched supply or
Via an addressable module.
Visual, audible and audio/visual models available
Red or white body available for audible alarm device
Operates when the supply voltage is connected to the device
Compatible with relay outputs from control and indicating equipment, or from an output module connected to addressable alarm circuit wiring
Dc 24 v operation
Loud sounder output of 85 db at 1 m
Long-life leds
Zero current load in quiescent condition
The 442 audio/visual alarm devices are suitable for connection to 2-wire and 4-wire fire detection and alarm systems.
441 will operate with both addressable and non-addressable fire detection control and indicating equipment.
Activation is initiated upon connection of the operating voltage, allowing connection to either a switched supply or via
An addressable module.
Visual, audible and audio/visual models available
Red or white body available for audible alarm device
Operates when the supply voltage is connected to the device
Compatible with relay outputs from control and indicating equipment, or from an output module connected to addressable alarm circuit wiring
Dc 24 v operation
Loud sounder output of 85 db at 1 m
Long-life leds
Zero current load in quiescent condition
Snd-500 dc smoke alarms provide battery powered smoke detection and alarm functions within a single unit.
Advanced electronics in conjunction with a photoelectric smoke sensing chamber provide early detection of fire
And high immunity against unwanted alarms.
Snd-500 dc smoke alarms are battery powered, do not require a mains supply, and are suitable for general
Residential applications.
Photoelectric smoke sensor
Integrated indicator provides visual indication of an alarm condition
Test button verifies battery and alarm operation
Loud 85 db sounder to alert occupants
Single dc 9 v user-replaceable battery provides up to 18 months operation under normal conditions
30 day low battery warning signal
Interconnection function available to connect up to 38 units together
Battery missing indicator
The 6001 analogue addressable control and indicating equipment forms the central part of a fire detection and alarm
System. The fully networkable 2-wire 6001 is compatible with numens addressable devices and can also be connected
To non-addressable devices when used with addressable input modules.
Default configuration programming facilitates out-of-box installation and rapid commissioning. A powerful and versatile
Cause-and-effect pc-based programming tool enables rapid customization with software for sites that
Require special operating features.
The 6001 comes standard with features that allows flexibility and expandability.
Single loop or 2-loop options available
Single loop, expandable to 2-loops available
Networkable, up to 4 control panels
Up to 125 addressable devices per loop
Automatic device detection on start-up
Automatic device type-code verification
2 independently programmable non-addressable a/v alarm output circuits
2 programmable fire alarm relay outputs
Fault relay output
Backlit lcd display providing 4 rows of 40 characters
16 zone fire alarm led indicators
3000 event history log
The 4001 non-addressable control and indicating equipment forms the central part of a fire detection and alarm
System. The 2-wire 4001 is compatible with numens non-addressable devices
The 4001 comes standard with features that allows flexibility and expandability. Default configuration programming
Facilitates out-of-box installation and rapid commissioning.
2, 4, 8, or 16 detection zones
Up to 32 non-addressable devices per alarm zone circuit
Configurable non-latching alarm zones, alarm dependency (zone coincidence detection), and output delay timer
3 access levels
Single-person test mode
Day/night mode
Manual activation of audio/visual alarm devices
Supervised auxiliary dc 24 v output
2 independently programmable non-addressable a/v alarm output circuits
2 programmable fire alarm relay outputs
Fault relay output
3 voltage-free inputs for remote reset, evacuation start/stop, and day/night mode
Supports up to 7 repeater panels
Sna-360 analogue addressable photoelectric smoke detectors are microprocessor controlled state-of-the-art detectors
Compatible with popular control and indicating equipment loop protocols.
Advanced electronics in conjunction with a photoelectric smoke sensing chamber provides early detection of fire and
High immunity against unwanted alarms.
Photoelectric smoke sensor
Analogue detection discrimination
Dual leds for 360° visibility
Dc 24 v operation
2-wire connection to many popular loop protocols
Dip switch address setting
125 usable detector address settings per loop
Optional remote led output
Hna-360 analogue addressable heat detectors are microprocessor controlled state-of-the-art detectors
Compatible with popular control and indicating equipment loop protocols.
An electronic thermistor sensor provides sensitive rate-of-rise alarm operation, or fixed-temperature operation
When the response threshold value is exceeded.
Durable heat sensor
Analogue detection discrimination
Dual leds for 360° visibility
Dc 24 v operation
2-wire connection to many popular loop protocols
Dip switch address setting
125 usable detector address settings per loop
Optional remote led output
HNC-310 non-addressable heat detectors are suitable for connection to 2-wire non-addressable fire detection
control and indicating equipment, or to addressable fire detection control and indicating equipment that can accept
non-addressable type detectors.
An electronic thermistor provides sensitive rate-of-rise operation or fixed-temperature operation when the response
threshold value is exceeded.
Durable heat sensor
Analogue detection discrimination
Dual LEDs for 360° visibility
2-wire and 4-wire models for DC 12 V and DC 24 V operation
Dual LEDs for 360° visibility
4-wire models available with a N/O alarm relay output
4-wire models available with auto-reset
2-wire models available with remote LED output
Connects to zone monitor for use with addressable control and indicating equipment
The 4001 non-addressable control and indicating equipment forms the central part of a fire detection and alarm
System.The 2-wire 4001 is compatible with numens non-addressable devices.
The 4001 comes standard with features that allows flexibility and expandability. Default configuration programming
Facilitates out-of-box installation and rapid commissioning.
2, 4, 8, or 16 detection zones
Up to 32 non-addressable devices per alarm zone circuit
Configurable non-latching alarm zones, alarm dependency (zone coincidence detection), and output delay timer
3 access levels
Single-person test mode
Day/night mode
Manual activation of audio/visual alarm devices
Supervised auxiliary dc 24 v output
2 independently programmable non-addressable a/v alarm output circuits
2 programmable fire alarm relay outputs
Fault relay output
3 voltage-free inputs for remote reset, evacuation start/stop, and day/night mode
Supports up to 7 repeater panels