Key Specifications/Special Features Ratings Power supply voltage Power consumption 24 VAC/DC: 1.8 VA/1 W max. 100 to 240 VAC: 2.5 VA max. Rated insulation voltage 600 VAC Operating value setting range (SV) 10% to 100% of maximum setting range Operating value 100% operation at set value Reset value setting range (HYS) 5% to 50% of operating value Reset method Note:Manual reset: Turn OFF power supply for 1 s or longer. Operating time setting range (T) 3to8 s Indicators Normal : Green light; Overvoltage Undervoltage : Yellow light Output form one Normally open and one normally closed Output relay ratings Rated load 5 A at 250 VAC (Resistive load) 5 A at 30 VDC (Resistive load) 1 A at 250 VAC (Inductive load) 0.2 A at 48 VDC (Inductive load) Minimum load: 5 VDC, 10 mA (reference values) Mechanical life: 10 million operations min. Electrical life: 5 A at 250 VAC or 30 VDC: 50,000 operations 3 A at 250 VAC or 30 VDC: 100,000 operations Ambient operating temperature -20 to 60°C (with no condensation or icing) Storage temperature -25 to 65°C (with no condensation or icing) Ambient operating humidity 25% to 85% RH (with no condensation) Storage humidity 25% to 85% RH (with no condensation) Altitude 2,000 m max. Applicable wires Stranded wires, solid wires, or ferrules Applicable wire size 0.25 to 1.5 mm2(AWG24 to AWG16) Wire insertion force 8 N max. for AWG20 wire Screwdriver insertion force 15 N max. Wire stripping length 8 mm Ferrule length 8 mm Current capacity 10 A (per pole) Weight Approx. 60 g Mounting Mounts to DIN Track Dimensions 30 � 60 �76 mm (W�H�D) Specifications Conforming standards EN 60947-5-1 Installation environment (pollution level 2, Overvoltage category III) Insulation resistance 20 MΩmin. Between external terminals and case Between power supply terminals and input terminals Between power supply terminals and output terminals Between input terminals and output terminals Dielectric strength 2,000 VAC for one minute Between external terminals and case Between power supply terminals and input terminals Between power supply terminals and output terminals Between input terminals and output terminals Impulse withstand voltage 6 kV (between live terminals and exposed, non-charged metal parts) Vibration resistance Frequency: 10 to 55 Hz, 0.35-mm single amplitude 10 sweeps of 5 min each in X,Y, and Z directions Shock resistance 100 m/s2, 3 times each in 6 directions along 3 axes Degree of protection Terminals: IP20 -