Radin Electric provides ATS design engineering and full after sales support for a wide range of automatic transfer switch applications. We offer onsite electrical audits to assist in determining the correct product and installation to meet your exact needs and requirements. a. Control power voltage AC 230V b. Auto Transfer Auto transfer auto recovery auto transfer no auto recovery power grid generator c. Manual transfer Manual main power manual backup power manual OFF d. Isolation lock Off position have isolation function also can padlock locked e. Generator control Generator start and stop f. Fire linkage With passove fire linkage signal to switch OFF the device with one set passive NO feedback contact. g. Display mode Mechanical indication device ON/OFF status operating mode LED device ON/OFF status power status LCD device ON/OFF status power status data setting h. Setting mode Key press operation Chinese/English display interface can set the working mode low voltage value over voltage value delay time auto transfer mode etc. i. Power monitoring ABC three phase over voltage (240 290v adjustable) ABC three phase low voltage (150 200v adjustable) ABC three phase missing monitor j. Delay time Transfer delay (0 300s adjustable) Recovery delay (0 300s adjustable) Generator start stop delay (0 300s adjustable) k. Mounting mode Integated mounting Controller Type A Basic type single phase monitor B. Standard type threee phase monitor fire fighting generator control C Intelligent type three phase monitor fire fighting generator control LCD display D Intelligent type three phase monitor fire fighting generator control split LCD display