LC 124 is an effective chlorine based designed for use in algae and bacteria control. It does not cause foaming. It is a concentrated blend of organo-chloro compounds which should be added only by slug feeding. Application: Use to control algae and bacteria in re-circulating commercial and industrial water cooling towers. Prior to its use, it is advisable that systems be cleaned to remove slime and other deposits. Dosage: An initial slug addition of 1 gallon of LC 124 per 2,000 gallons of water should be employed every 1-4 days or as needed. The frequency of addition depends upon the relative amount of bleed-off and the severity of the microbiological problem. Slug additions should be made in the sump of the cooling tower. During very hot weather, greater frequency or higher dosage may be required to increase its effectiveness. Handling & Precaution: It is a very strong treatment and may cause eye damage, mucous attack and skin irritation. Do not inhale, get in eyes, skin or on clothing. Wear goggles or face shield and rubber gloves when handling. Avoid contamination of food. Harmful or fatal if swallowed. In case of skin contact, wash with plenty of soap and water. Remove contaminated clothing and wash before reuse. If product gets in the eyes, flush immediately with copious amount of clean cool water for at least 15 minutes. If swallowed, call physician. Do not induce vomiting or give anything by mouth to an unconscious person. Packaging: Available in pail of 20 lt.. Can also becustom packaged.